Plan Review Notes
Plan Review Notes For Permit 05031840
Permit Number 05031840
Review Stop E
Sequence Number 5
Notes
Date Text
2006-07-22 00:00:00*** REDLINED PLANS ***
  
 TO BE REVISED BEFORE FINAL/ C.O.
  
 1) NOTE: PLEASE SEE DINING RM CIRUIT
 SHOWN AT 1000VA WHEN 1500VA MIN IS
 REQUIRED PER 210.52B1,210.11C1,220.16
  
 2) NOTE: PLEASE SEE CU CIRCUIT SHOWS
 1000VA ON ONE PHASE AND 1500 VA ON THE
 OTHER. THIS IS NOT POSSIBLE. PLEASE
 ADJUST LOADS AND VA.
 408.4, 240.4, ETC
 106.1.2 FBC.
  
 3) NOTE: PLEASE SEE ITEMS SHOWN AS
 1-POLE/2-POLE??
  
 4) NOTE: PLEASE VERIFY THE LOCATION OF
 SD REQUIRED IN THE IMMEDICATE VICINITY
 OUTSIDE BEDRMS#2, AND #3. SEE NFPA-72
 11.5.1.1,11.8.3.
  
 5) NOTE: PLEASE SEE GD OPENER SHOWS
 1000VA ON LOAD CALCULATIONS, YET SHOWS
 1200VA ON PANEL SCHEDULE? PLEASE
 CORRELATE AND ADJUST.
 408.4, 106.1.2
  
 6) NOTE: VERIFY DEN CIRCUIT AS THIS
 SHOWS 15A BRKR AND #12 AWG. THIS IS OK,
 HOWEVER IF SHOWN THIS WAY THEN THIS WILL
 BE VERIFIED.
  
 7) NOTE: PLEASE SEE THE DISHPOSAL AND
 DISHWASHER IS ONLY TO VERIFY IF THESE
 ARE BOTH ON SEPARATE RECEPTS. IF BOTH
 ARE FED TO ONE RECEPTS, THEN THIS RECEPT
 MUST BE FED FROM A TWO POLE BREAKER.
 PLEASE ONLY REVISED PANEL SCHEDULE FOR
 2-POLE BRKR IF INDEED ONE DEVICE/RECEPT
 FEEDS BOTH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL CO. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE TO
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  