2006-07-22 00:00:00 | *** REDLINED PLANS *** |
| |
| TO BE REVISED BEFORE FINAL/ C.O. |
| |
| 1) NOTE: PLEASE SEE DINING RM CIRUIT |
| SHOWN AT 1000VA WHEN 1500VA MIN IS |
| REQUIRED PER 210.52B1,210.11C1,220.16 |
| |
| 2) NOTE: PLEASE SEE CU CIRCUIT SHOWS |
| 1000VA ON ONE PHASE AND 1500 VA ON THE |
| OTHER. THIS IS NOT POSSIBLE. PLEASE |
| ADJUST LOADS AND VA. |
| 408.4, 240.4, ETC |
| 106.1.2 FBC. |
| |
| 3) NOTE: PLEASE SEE ITEMS SHOWN AS |
| 1-POLE/2-POLE?? |
| |
| 4) NOTE: PLEASE VERIFY THE LOCATION OF |
| SD REQUIRED IN THE IMMEDICATE VICINITY |
| OUTSIDE BEDRMS#2, AND #3. SEE NFPA-72 |
| 11.5.1.1,11.8.3. |
| |
| 5) NOTE: PLEASE SEE GD OPENER SHOWS |
| 1000VA ON LOAD CALCULATIONS, YET SHOWS |
| 1200VA ON PANEL SCHEDULE? PLEASE |
| CORRELATE AND ADJUST. |
| 408.4, 106.1.2 |
| |
| 6) NOTE: VERIFY DEN CIRCUIT AS THIS |
| SHOWS 15A BRKR AND #12 AWG. THIS IS OK, |
| HOWEVER IF SHOWN THIS WAY THEN THIS WILL |
| BE VERIFIED. |
| |
| 7) NOTE: PLEASE SEE THE DISHPOSAL AND |
| DISHWASHER IS ONLY TO VERIFY IF THESE |
| ARE BOTH ON SEPARATE RECEPTS. IF BOTH |
| ARE FED TO ONE RECEPTS, THEN THIS RECEPT |
| MUST BE FED FROM A TWO POLE BREAKER. |
| PLEASE ONLY REVISED PANEL SCHEDULE FOR |
| 2-POLE BRKR IF INDEED ONE DEVICE/RECEPT |
| FEEDS BOTH. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW BEFORE FINAL CO. IF THERE ARE ANY |
| QUESTIONS, PLEASE DO NOT HESITATE TO |
| CALL. |
| |