Notes |
Date |
Text |
2006-07-18 00:00:00 | ********* UNSAT *********** | | | | 1) NOTE: PLEASE CORRELATE ALL ITEMS | | INDICATED ON LOAD CALCUALITONS WITH | | PANEL SCHEDULE AND ITEMS ON PANEL | | SCHEDULE WITH LOAD CALCUALTIONS. | | 408.4,310.16,220.31 ETC | | | | 2) NOTE: PLEASE SEE ALL CIRCUITS ON | | PANEL SCHEDULE. PLEASE CORRELATE ALL | | LOADS WITH THE CORRECT OCP AND CONDUCTOR | | SIZES. PLEASE SEE THERE ARE NUMEROUS | | ITEMS WHICH DO NOT CORRELATE. | | 60A OCP ON #10, | | LOADS EXCEEDING OCP AND WIRE SIZE. | | 8KW ON #12, | | 5KW ON #12, | | WIRE SHOWN AS #154? | | PLEASE SEE MIN VA FOR SM APPLIANCE | | CIRCUITS TO BE 1500VA MIN. | | PLEASE LABEL SMALL APPLIANCE | | CIRCUITS(KITCHEN OUTLETS0?? | | | | ** PLEASE KNOW, THIS SEEMS TO BE A | | MISPRINTING OF THESE ITEMS. | | PLEASE BE SURE TO GO THROUGH ALL | | CIRCUITS WHICH ARE REQUIRED TO BE 20A | | FOR WASHER, SM APPLIANCE, LAUNDRY , | | DINING RM ETC AND BE SURE THE WIRE SIZE | | CORRELATES ETC. | | | | 310.16,240.4,408.4, 210.52B1, 210.11C1, | | 220.16 ETC | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|