Plan Review Notes
Plan Review Notes For Permit 05031840
Permit Number 05031840
Review Stop E
Sequence Number 4
Notes
Date Text
2006-07-18 00:00:00********* UNSAT ***********
  
 1) NOTE: PLEASE CORRELATE ALL ITEMS
 INDICATED ON LOAD CALCUALITONS WITH
 PANEL SCHEDULE AND ITEMS ON PANEL
 SCHEDULE WITH LOAD CALCUALTIONS.
 408.4,310.16,220.31 ETC
  
 2) NOTE: PLEASE SEE ALL CIRCUITS ON
 PANEL SCHEDULE. PLEASE CORRELATE ALL
 LOADS WITH THE CORRECT OCP AND CONDUCTOR
 SIZES. PLEASE SEE THERE ARE NUMEROUS
 ITEMS WHICH DO NOT CORRELATE.
 60A OCP ON #10,
 LOADS EXCEEDING OCP AND WIRE SIZE.
 8KW ON #12,
 5KW ON #12,
 WIRE SHOWN AS #154?
 PLEASE SEE MIN VA FOR SM APPLIANCE
 CIRCUITS TO BE 1500VA MIN.
 PLEASE LABEL SMALL APPLIANCE
 CIRCUITS(KITCHEN OUTLETS0??
  
 ** PLEASE KNOW, THIS SEEMS TO BE A
 MISPRINTING OF THESE ITEMS.
 PLEASE BE SURE TO GO THROUGH ALL
 CIRCUITS WHICH ARE REQUIRED TO BE 20A
 FOR WASHER, SM APPLIANCE, LAUNDRY ,
 DINING RM ETC AND BE SURE THE WIRE SIZE
 CORRELATES ETC.
  
 310.16,240.4,408.4, 210.52B1, 210.11C1,
 220.16 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]