2006-07-07 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PANEL SCHEDULE WITH THE ACTUAL
 CIRCUIT NUMBERS. PLEASE SEE 2-POLE
 CIRCUITS SHOULD INDEED TAKE THE SPACE OF
 TWO CIRCUITS SPACES ON PANEL SCHEDULE.
 PLEASE KNOW, ALL CIRCUITS FOR ROOMS AND
 AREAS SHALL BE INDICATE ON PANEL
 SCHEDULE SPECIFIC TO THE ROOM ETC.
 IE; LTS BRM, RECEPTS MASTER BEDRM, BATH
 #2 LTS. ETC
  
 2) NOTE: PLEASE SEE SD IN MSTER BEDRM IS
 REQUIRED TO BE LOCATED WITHIN 12" OF THE
 HIGHTEST POINT ON A FLAT CEILING.
 NFPA-72 11.8.3
  
 3) NOTE: PLEASE BE SURE PLANS CONTAIN
 THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR PLANS/DEISGN.
 FBC ADMIN SECT 104.2.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]