2005-04-06 00:00:00 | ************ UNSAT ************** |
| |
| 1)NOTE: PLEASE INCLUDE INFORMATION FOR |
| MAIN. IS PANEL A MCB ? IS MAIN LOCATED |
| WITH METER? |
| 215.5,240.4B,225.30 ETC. |
| |
| 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 3)NOTE: PLEASE SEE IF MAIN IS NOT |
| LOCATED AT METER, PLEASE SEE 250.6, |
| 250.24, AN EQUIPMENT GROUNDING CONDUCTOR |
| IS NOT INSTALLED FROM METER TO FIRST |
| MEANS OF DISCONNECT. |
| PLEASE SEE RISER SHOWS AN EQUIPMENT |
| GROUNDING CONDCUTOR FROM METER TO MAIN. |
| |
| 4)NOTE: PLEASE SEE RISER INDICATES A |
| POSSIBLE SUB-PANEL IF REQUIRED. IF THIS |
| IS INSTALLED, PLANS BE NEED TO BE |
| REVISED TO REFLECT ACTUAL INSTALLATION |
| TAKEN. |
| PLEASE ALSO SEE PANEL IS SHOWN WITH #5 |
| AS FEEDERS. PLEASE SEE AWG'S AVAILABLE, |
| THIS IS NOT A SIZE. PLEASE SEE 310.16 |
| |
| 5)NOTE: PLEASE SEE MISSING RECEPTS ALONG |
| KITCHEN COUNTERSPACE PER 210.52C1 |
| PLEASE SHOW ALL RECEPTS SERVING KITCHEN |
| COUNTERSPACE AS GFI/GFI PROTECTED PER |
| 210.8A-6 |
| |
| |
| 6)NOTE: PLEASE CORRELATE PANEL SCHEDULE |
| AND LOAD CALCAULTIONS. PLEASE SEE THERE |
| ARE NUMEROUS ITEMS THAT DO NOT |
| CORRELATE. |
| IE: WELL PUMNP, DISPOSAL, FRIG, A/C |
| UNITS, DISHWASHER, WASHER/LANUDRY, |
| RANGE, ETC. |
| |
| 7)NOTE: PLEASE ALSO SEE MANY "MISPRINTS" |
| ON PANEL SCHEDULE. PLEASE SEE 2-POLE |
| CIRCUITS, SHOWING A REDUCED AWG AND OCP |
| ON "B" PHASE. |
| |
| 8)NOTE: PLEASE CORRELATE PLANS, PANEL |
| SCHEDULE AND LOAD CALCULATIONS FOR |
| RANGE, OVENS. |
| PLEASE SEE PLANS INDICATE DOUBLE OVENS, |
| YET THIS IS NOT ON PANEL SCHEDULE OR |
| LOAD CALCS. PLEASE SEE PLANS INDICATE A |
| SEPARATE COOKTOP ALSO, YET THIS IS NOT |
| ON PANEL SCHEDULE OR LOAD CALCS. |
| PLEASE SEE PANEL SCHEDULE SHOWS 13KW2-P |
| 60A FOR RANGE??? |
| PLEASE SEE LOAD CALCS SHOWS 8KW? |
| ETC. |
| |
| 9)NOTE: PLEASE SEE PLANS FOR MISSING |
| RECEPTS PER 210.52 |
| |
| 10)NOTE: PLEASE SEE MISSING DISCONNECT |
| FOR A/C COND UNIT PER 440.11 |
| PLEASE SHOW. |
| |
| 11)NOTE: PLEASE SEE FBC 104.2.1, WHICH |
| REQUIRES THE PRINTED NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR PLANS. |
| PLEASE THE PLANS ONLY NEED THE PRINTED |
| NAME. |
| |
| 12)NOTE: PLEASE SEE ONE SET OF PLANS HAS |
| BEEN REDLINED AT LOCATIONS FOR THE ABOVE |
| COMMENTS. PLEASE SEE THESE LOACTIONS |
| SHOWN ON PLANS. |
| |
| 13)NOTE: PLEASE REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETED SETS FOR |
| REVIEW AND STAMPING. |
| PLEASE SUBMIT ONE SET OF OLD/VOIDED |
| SHEETS FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |