Plan Review Notes
Plan Review Notes For Permit 05031654
Permit Number 05031654
Review Stop B
Sequence Number 2
Notes
Date Text
2005-05-19 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE TYPICAL WALL SECTION ON SHEET A2
 SPECIFIES 2X8 #2 SYP FOR THE CEILING
 JOISTS AND SECTION 3 ON A3 CALLS FOR
 2X10 #2 DENSE SYP. REVISE PLANS TO
 INDICATE WHICH ONE IS TO BE USED.
  
 3) THE ROOF NOTES ON A3 REFER TO ROOF
 TRUSSES AND STATE THAT TRUSS ENGINEER IS
 RESPONSIBLE FOR THE FINAL ROOF AND FLOOR
 TRUSS LAYOUT. IF MANUFACTURED TRUSSES
 ARE NOT BEING USED PLEASE REVISE OR
 REMOVE THESE NOTES AS THEY DO NOT
 PERTAIN TO THE DESIGN OF THIS PROJECT.
  
 4) SPECIFY COLLAR BEAMS OF 1X6 BOARDS
 INSTALLED TO EVERY THIRD PAIR OF RAFTERS
 AS REQUIRED BY FBC 2309.1.7.
  
 5) FLOOR JOISTS ARE REQUIRED TO BE
 SUPPORTED LATERALLY AT THE ENDS BY SOLID
 BLOCKING OR DIAGONAL STRUTS OR OTHER
 METHOD. PLEASE SPECIFY METHOD THAT WILL
 BE USED. SEE FBC 2307.3.4.
  
 6) SUBMIT THE NOA OR EVALUATION REPORTS
 AND INSTALLATION INSTRUCTIONS IN
 ADDITION TO THE STATE COVERSHEETS FOR
 THE SINGLE HUNG WINDOWS AND THE STORM
 PANELS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  