Plan Review Notes For Permit 05031573 |
Permit Number |
05031573 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-04-13 00:00:00 | 1) A MINIMUM OF TWO SETS OF DRAWINGS ARE | | REQUIRED. | | | | 2) EXIT SIGNS AND EMERGENCY LIGHTS ARE | | TO BE HARDWIRED TO THE BUILDING | | ELECTRICAL SYSTEM WITH BATTERY BACK UP. | | | | 3) AN ADDRESS NUMBER IS REQUIRED TO BE | | AT LEAST 6" IN HEIGHT AND CONTRASTING TO | | THE BACKGROUND. | | | | 4) ARE THERE STEPS AND RAILINGS OUTSIDE | | OF THE EXIT DOORS? IF SO, PLEASE INCLUDE | | DETAILS. | | | | 5) PLAN IS NOT DRAWN TO SCALE. WHAT ARE | | THE WIDTHS OF THE EXIT DOORS? | | | | 6) HOW DOES THE TRAILER SIT ON THIS SITE | | IN REGARDS TO OTHER STRUCTURES? | | | | | | MIKE WENNERGREN, A/CAPTAIN | | WPBFR(561) 835-2910 OR 805-6722 |
|