Plan Review Notes
Plan Review Notes For Permit 05031504
Permit Number 05031504
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-05-04 00:00:001) ALL LIFE SAFETY MUST COMPLY WITH NFPA
 101, 2003 EDITION.
  
 2) THE PARKING GARAGE SHALL MAINTAIN A 2
 HOUR SEPARATION FROM OTHER AREAS OF THE
 BUILDING AND COMPLY WITH NFPA 88A.
  
 3) THE DOOR APPEARS TO BE MISSING AT THE
 STAIRWELL ADJACENT TO THE OFFICE. 1ST
 LEVEL TOWNHOUSE/PARKING.
  
 4) THE DOOR SWING INTO STAIR #4 APPEARS
 TO BE AGAINST THE PATH OF TRAVEL.
  
 5) ARE ALL MAXIMUM TRAVEL DISTANCES IN
 ACCORDANCE WITH NFPA 101, 2003 EDITION?
  
 6) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 7) SINCE THE BUILDING EXCEEDS 75' IN
 HEIGHT, IT MUST COMPLY WITH BUILDING AND
 FIRE CODE REQUIREMENTS FOR HIGHRISE
 BUILDINGS.
  
 8) THE LOWER PARKING PLAN SHOWS ONLY ONE
 EXIT AT STAIR #4. PLEASE EXPLAIN.
  
 9) THE DOORS TO THE ELETRIC ROOMS
 APPEAR TO OBSTRUCT THE CORRIDORS GREATER
 THAN 1/2 THE TOTAL WIDTH.
  
 10) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES 3 STORIES OR
 30' IN HEIGHT.
  
 11) TWO UNITS ON THE SOUTH SIDE OF THE
 BUILDING HAVE 300 ADDRESSES ON THE 4TH
 FLOOR.
  
 12) TWO UNITS ON THE SOUTH SIDE OF THE
 BUILDING HAVE 500 ADDRESSES ON THE 6TH
 FLOOR.
  
 13) ALL SHAFTS THAT ARE LARGE ENOUGH FOR
 PERSONS TO FALL INTO MUST BE MARKED
 SHAFTWAY IN 6" LETTERS.
  
 14) TACTILE SIGNAGE IS REQUIRED AT EXIT
 DOORS.
  
 15) AN ADDRESS NUMBER IS REQUIRED THAT
 IS A MINMUM OF 6" IN HEIGHT AND
 CONTRASTING TO THE BACKGROUND.
  
 16) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 17) SIGNS ARE REQUIRED IN THE STAIRWELLS
 INDICATING TOP, BOTTOM, FLOOR NUMBER,
 ROOF ACCESS AND THE IDENTITY.
  
 18) PLEASE PROVIDE MORE DETAILS ON THE
 AWNINGS IN REGARDS TO OVERHANG HEIGHT
 AND FIRE RETARDANT INFORMATION.
  
 19) PLEASE PROVIDE OCCUPANT LOAD
 CALCULATIONS FOR THE POOL DECK AREA.
  
 20) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION OF THE WALLS AND
 CEILINGS.
  
 21) THE ELEVATOR/FIRE ALARM NOTES MAKES
 REFERENCE TO FLOORS 2-25. PLEASE MAKE
 CORRECTION.
  
 22) EMERGENCY LIGHTING FACILITIES ARE
 MISSING FROM ALL COMMON AREAS AND OTHER
 LOCATIONS ROUTINELY INHABITED BY HUMANS
 WITH THE EXCEPTION OF THE STAIRWELLS.
  
 23) IF THE TOTAL NUMBER OF SPRINKLERS
 EXCEEDS 1000, A MINIMUM OF 24 SPARE
 SPRINKLERS IS REQUIRED, NOT 6.
  
 24) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS.
  
 25) LOCKING KNOX BOX CAPS ARE REQUIRED
 FOR THE FIRE DEPARTMENT CONNECTIONS.
  
 26) KNOX BOXES WILL BE REQUIRED.
  
 27) THE FIRE ALARM SYSTEM SHALL MEET THE
 MONITORING REQUIREMENTS FOR CENTRAL
 STATION SERVICE.
  
 28) PLEASE DISPLAY ANY EXISTING OR NEW
 FIRE HYDRANTS IN THE VICINITY OF THE
 BUIDING.
  
 29) HIGHRISE BUILDINGS ARE REQUIRED TO
 HAVE TWO FIRE DEPARTMENT CONNECTIONS.
  
 30) THE FIRE DEPARTMENT CONNECTIONS CAN
 BE NO FURTHER THAN 150' FROM THE CLOSEST
 FIRE HYDRANT.
  
 31) THE FIRE PROTECTION DRAWINGS DON'T
 SHOW FIRE SPRINKLER PROTECTION IN ALL
 THE LIVING UNITS.
  
 32) THE FIRE ALARM SYSTEM SHALL BE CLASS
 A STYLE D OR FULLY ADDRESSABLE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR9%61) 835-2910 OR 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  