Date |
Text |
2005-05-04 00:00:00 | 1) ALL LIFE SAFETY MUST COMPLY WITH NFPA |
| 101, 2003 EDITION. |
| |
| 2) THE PARKING GARAGE SHALL MAINTAIN A 2 |
| HOUR SEPARATION FROM OTHER AREAS OF THE |
| BUILDING AND COMPLY WITH NFPA 88A. |
| |
| 3) THE DOOR APPEARS TO BE MISSING AT THE |
| STAIRWELL ADJACENT TO THE OFFICE. 1ST |
| LEVEL TOWNHOUSE/PARKING. |
| |
| 4) THE DOOR SWING INTO STAIR #4 APPEARS |
| TO BE AGAINST THE PATH OF TRAVEL. |
| |
| 5) ARE ALL MAXIMUM TRAVEL DISTANCES IN |
| ACCORDANCE WITH NFPA 101, 2003 EDITION? |
| |
| 6) CONSTRUCTION, ALTERATION AND |
| DEMOLITION TO COMPLY WITH NFPA 241. |
| |
| 7) SINCE THE BUILDING EXCEEDS 75' IN |
| HEIGHT, IT MUST COMPLY WITH BUILDING AND |
| FIRE CODE REQUIREMENTS FOR HIGHRISE |
| BUILDINGS. |
| |
| 8) THE LOWER PARKING PLAN SHOWS ONLY ONE |
| EXIT AT STAIR #4. PLEASE EXPLAIN. |
| |
| 9) THE DOORS TO THE ELETRIC ROOMS |
| APPEAR TO OBSTRUCT THE CORRIDORS GREATER |
| THAN 1/2 THE TOTAL WIDTH. |
| |
| 10) TEMPORARY STANDPIPES ARE REQUIRED |
| WHEN THE BUILDING REACHES 3 STORIES OR |
| 30' IN HEIGHT. |
| |
| 11) TWO UNITS ON THE SOUTH SIDE OF THE |
| BUILDING HAVE 300 ADDRESSES ON THE 4TH |
| FLOOR. |
| |
| 12) TWO UNITS ON THE SOUTH SIDE OF THE |
| BUILDING HAVE 500 ADDRESSES ON THE 6TH |
| FLOOR. |
| |
| 13) ALL SHAFTS THAT ARE LARGE ENOUGH FOR |
| PERSONS TO FALL INTO MUST BE MARKED |
| SHAFTWAY IN 6" LETTERS. |
| |
| 14) TACTILE SIGNAGE IS REQUIRED AT EXIT |
| DOORS. |
| |
| 15) AN ADDRESS NUMBER IS REQUIRED THAT |
| IS A MINMUM OF 6" IN HEIGHT AND |
| CONTRASTING TO THE BACKGROUND. |
| |
| 16) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| REQUIREMENTS FOR ALL HANDRAILS AND |
| GUARDRAILS. |
| |
| 17) SIGNS ARE REQUIRED IN THE STAIRWELLS |
| INDICATING TOP, BOTTOM, FLOOR NUMBER, |
| ROOF ACCESS AND THE IDENTITY. |
| |
| 18) PLEASE PROVIDE MORE DETAILS ON THE |
| AWNINGS IN REGARDS TO OVERHANG HEIGHT |
| AND FIRE RETARDANT INFORMATION. |
| |
| 19) PLEASE PROVIDE OCCUPANT LOAD |
| CALCULATIONS FOR THE POOL DECK AREA. |
| |
| 20) PLEASE PROVIDE INTERIOR FINISH |
| CLASSIFICATION OF THE WALLS AND |
| CEILINGS. |
| |
| 21) THE ELEVATOR/FIRE ALARM NOTES MAKES |
| REFERENCE TO FLOORS 2-25. PLEASE MAKE |
| CORRECTION. |
| |
| 22) EMERGENCY LIGHTING FACILITIES ARE |
| MISSING FROM ALL COMMON AREAS AND OTHER |
| LOCATIONS ROUTINELY INHABITED BY HUMANS |
| WITH THE EXCEPTION OF THE STAIRWELLS. |
| |
| 23) IF THE TOTAL NUMBER OF SPRINKLERS |
| EXCEEDS 1000, A MINIMUM OF 24 SPARE |
| SPRINKLERS IS REQUIRED, NOT 6. |
| |
| 24) SEPARATE SHOP DRAWINGS AND PERMITS |
| ARE REQUIRED FOR THE FIRE ALARM AND FIRE |
| SPRINKLER SYSTEMS. |
| |
| 25) LOCKING KNOX BOX CAPS ARE REQUIRED |
| FOR THE FIRE DEPARTMENT CONNECTIONS. |
| |
| 26) KNOX BOXES WILL BE REQUIRED. |
| |
| 27) THE FIRE ALARM SYSTEM SHALL MEET THE |
| MONITORING REQUIREMENTS FOR CENTRAL |
| STATION SERVICE. |
| |
| 28) PLEASE DISPLAY ANY EXISTING OR NEW |
| FIRE HYDRANTS IN THE VICINITY OF THE |
| BUIDING. |
| |
| 29) HIGHRISE BUILDINGS ARE REQUIRED TO |
| HAVE TWO FIRE DEPARTMENT CONNECTIONS. |
| |
| 30) THE FIRE DEPARTMENT CONNECTIONS CAN |
| BE NO FURTHER THAN 150' FROM THE CLOSEST |
| FIRE HYDRANT. |
| |
| 31) THE FIRE PROTECTION DRAWINGS DON'T |
| SHOW FIRE SPRINKLER PROTECTION IN ALL |
| THE LIVING UNITS. |
| |
| 32) THE FIRE ALARM SYSTEM SHALL BE CLASS |
| A STYLE D OR FULLY ADDRESSABLE. |
| |
| |
| MIKE WENNERGREN, A/CAPTAIN |
| WPBFR9%61) 835-2910 OR 805-6722 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |