2005-05-02 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- PAY IMPACT FEES. BRING BACK STAMPED |
| DRAWINGS AND PAID RECEIPT. |
| |
| 2- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 3- DESIGNER OF RECORD TO SPECIFY ROOF |
| TILE FASTENING AS REQUIRED BY SECTION |
| 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
| |
| 4- WEST ELEVATION DON'T MATCH FLOOR |
| PLAN. SEE CORRIDOR BETWEEN FOYER AND |
| BEDROOM #3. REVISE AS REQUIRED. |
| |
| 5- PROVIDE COMPLETE SPECS AND DETAILS |
| FOR STRUCTURAL COLUMNS IN FOYER AREA. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| 6- ENTRY DOORS (101 AND 112) TO PROVIDE |
| 32" MIN. CLEAR OPENING PER LEAF AS REQ'D |
| BY TABLE 1004 FBC 2001. REVISE AS REQ'D. |
| |
| 7- NEED AT LEAST ONE BEDROOM WITH |
| BATHROOM DOOR THAT PROVIDES 29" MINIMUM |
| CLEAR OPENING AS REQ'D BY SEC. 11-11 FBC |
| |
| 8- PROVIDE COMPLETE DETAILS AND SPECS |
| FOR WOOD TRELLIS AT KITCHEN DECK. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 9- PROVIDE A/C CHASE DETAIL ON BEAM B-1. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| 10- CONNECTORS MTS18 AND MSTA21 DON'T |
| HAVE LATERAL LOADS. HOW ARE TRUSS |
| LATERAL LOADS RESISTED? SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| |
| 11- PROVIDE FLORIDA OR APPLY FOR LOCAL |
| PRODUCT APPROVAL FOR: |
| A) ENTRY DOORS. |
| B) SINGLE HUNG WINDOWS. |
| C) SPECIFY WHERE ARE THE THERMA-TRU |
| DOORS GOING TO BE INSTALLED. |
| D) KITCHEN DOOR. |
| E) FLAT ROOF SYSTEM. |
| F) ROOF TILE: NEED SBCCI REPORT THAT WAS |
| SUBMITTED FOR FLORIDA APPROVAL. |
| G) FRENCH DOORS. DADE COUNTY NOA ALONE |
| IS NOT FLORIDA PRODUCT APPROVAL. |
| |
| 12- PROVIDE COMPLETEFLUELESS FIREPLACE |
| LISTING AND SPECIFICATIONS AS REQUIRED |
| BY SEC. 2806 FBC 2001. |
| |
| 13- ENERGY CALCULATIONS: PROVIDE |
| COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING ADDRESS ETC. |
| |