Plan Review Notes
Plan Review Notes For Permit 05031409
Permit Number 05031409
Review Stop B
Sequence Number 1
Notes
Date Text
2005-04-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05031409
 ADD: 2800 N FLAGLER/ 705
 CONT:MO JO EBERBACH
 TEL: (561)644-8425
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) WORK OUT OF SCOPE OF LICENSE, NO WORK
 CAN BE COMPLETED ON THE EXTERIOR OF THE
 BUILDING (WINDOW/ DOOR REPLACEMENT) WITH
 A CBC LICENSE. SEE ATTACHMENT. A CGC
 WILL HAVE TO MAKE APPLICATION FOR THE
 REPLACEMENT OF SLIDING GLASS DOORS.
  
 2)A NEW NOCWITH CGC,PROVIDE NOC
 RECORDED WITH THE CLERK OF COURT BEFORE
 A PERMIT CAN BE ISSUED.
  
 3) THE LA FONTANA IS A HIGH-RISE,
 PROVIDE HOW MANY STORIES OR IN FT THE
 BUILDING IS TALL, INDICATE IF THE UNIT
 WORK IS TO BE COMPLETE IN IS IN THE
 INTERIOR ZONE OR END ZONE. PROVIDE THE
 NEGATIVE PRESSURES FOR NEW SLIDING GLASS
  
 DOOR.
  
 4)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) 609.2.1 TYPE I OR II BLDG, ALL
 PARTITIONS SHALL BE CONSTRUCTED FROM
 NONCOMBUSTIBLE MATERIALS.
  
 6) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  