Plan Review Notes For Permit 05031189 |
Permit Number |
05031189 |
|
Review Stop |
E |
Sequence Number |
7 |
|
Notes |
Date |
Text |
2006-10-19 07:27:49 | | | | | REVISION DENIED | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} THE RISER DIAGRAM INDICATES PANEL "P" BEING FED FROM | | PANEL "A". THE PANEL SCHEDULE INDICATES PANEL "P" FED | | FROM PANEL "B", PLEASE CORRELATE. | | | | 2} THE FEED TO PANEL "P" MUST CONTAIN AN EQUIPMENT | | GROUND PER 250.122, #10CU. | | | | 3} THE QUALITY OF THE REVISION SUBMITTED IS | | INSUFFICIENT FOR RECORD RETANTION PER 106.1.3 FBC AS | | AMENDED. | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|