Date |
Text |
2005-08-10 00:00:00 | BUILDING REVIEW THIRD CHECKLIST: |
| 1- ENERGY CALCULATIONS ARE STILL WRONG. |
| (SEE COPY OF FLORIDA STATUTE |
| 553.80(2)(B)REGARDING DESIGN |
| PROFESSIONAL DOCUMENTS).OVERHANG LENGTH |
| AND HEIGHT ARE STILL WRONG. SEE SEC. |
| 601.2 OF CHAPTER 13 FBC. |
| **NOTE: ARCHITECT ALSO NEEDS TO IMPRESS |
| HIS SEAL IN ALL DOCUMENTS THAT ARE |
| SUBMITTTED FOR PUBLIC RECORDS AS REQ'D |
| BY CHAPTER 481 FLORIDA STATUTES. |
| |
| 2- PROVIDE FLORIDA OR APPLY FOR LOCAL |
| PRODUCT APPROVAL FOR: |
| A) POCKET SLIDING GLASS DOORS AS SHOWN |
| ON PLANS. |
| |
| B) BAY WINDOW FOR BREAKFAST AREA. |
| PRODUCT APPROVAL SUBMITTED DOESN'T COVER |
| SIZE SPECIFIED ON PLANS FOR BREAKFAST |
| AREA. |
| |
| C) EYEBROW WINDOW ASSEMBLY AS SHOWN ON |
| LIVING ROOM. |
| |
| D) CASEMENT WINDOWS. NEED DADE COUNTY |
| NOA REPORT THAT MATCHES ONE SUBMITTED |
| FOR FLORIDA PRODUCT APPROVAL. |
| |
| E) ALL TRUSS CONNECTORS SPECIFIED ON |
| PLANS. |
| |
| 3- SIZE OF LIVING ROOM WINDOW SPECIFIED |
| ON SHEET A1 DOESN'T MATCH SIZE SHOWN ON |
| THE REAR ELEVATION. REVISE/CLARIFYAS |
| REQUIRED TO VERIFY PRODUCT APPROVAL |
| COMPLIANCE. |
| |
| 4- SHEET A1: A) NOTE ON GARAGE ATTIC |
| STORAGE IS WRONG. IT SHOULD BE 30PSF |
| ATTIC LIVE LOAD NOT 30PSF DEAD LOAD. |
| REVISE AS REQ'D. TABLE 1604.1 FBC 2001. |
| |
| B) WINDOW GLAZING NOTE: REFERENCED SEC. |
| #3513 DOESN'T APPLY. REVISE AS REQUIRED. |
| |
| 5- SLIDING GLASS DOOR POCKET DETAIL. |
| PREVIOUS CHECKLIST REQUIRED TO SPECIFY |
| 7/8" MIN. STUCCO THICKNESS AS REQUIRED |
| BY ASTM C-926. DETAIL WAS REVISED TO |
| HAVE 7/8" CDX PLYWOOD INSTEAD. REVISE AS |
| REQUIRED. |
| |