Plan Review Notes
Plan Review Notes For Permit 05031189
Permit Number 05031189
Review Stop B
Sequence Number 3
Notes
Date Text
2005-08-10 00:00:00BUILDING REVIEW THIRD CHECKLIST:
 1- ENERGY CALCULATIONS ARE STILL WRONG.
 (SEE COPY OF FLORIDA STATUTE
 553.80(2)(B)REGARDING DESIGN
 PROFESSIONAL DOCUMENTS).OVERHANG LENGTH
 AND HEIGHT ARE STILL WRONG. SEE SEC.
 601.2 OF CHAPTER 13 FBC.
 **NOTE: ARCHITECT ALSO NEEDS TO IMPRESS
 HIS SEAL IN ALL DOCUMENTS THAT ARE
 SUBMITTTED FOR PUBLIC RECORDS AS REQ'D
 BY CHAPTER 481 FLORIDA STATUTES.
  
 2- PROVIDE FLORIDA OR APPLY FOR LOCAL
 PRODUCT APPROVAL FOR:
 A) POCKET SLIDING GLASS DOORS AS SHOWN
 ON PLANS.
  
 B) BAY WINDOW FOR BREAKFAST AREA.
 PRODUCT APPROVAL SUBMITTED DOESN'T COVER
 SIZE SPECIFIED ON PLANS FOR BREAKFAST
 AREA.
  
 C) EYEBROW WINDOW ASSEMBLY AS SHOWN ON
 LIVING ROOM.
  
 D) CASEMENT WINDOWS. NEED DADE COUNTY
 NOA REPORT THAT MATCHES ONE SUBMITTED
 FOR FLORIDA PRODUCT APPROVAL.
  
 E) ALL TRUSS CONNECTORS SPECIFIED ON
 PLANS.
  
 3- SIZE OF LIVING ROOM WINDOW SPECIFIED
 ON SHEET A1 DOESN'T MATCH SIZE SHOWN ON
 THE REAR ELEVATION. REVISE/CLARIFYAS
 REQUIRED TO VERIFY PRODUCT APPROVAL
 COMPLIANCE.
  
 4- SHEET A1: A) NOTE ON GARAGE ATTIC
 STORAGE IS WRONG. IT SHOULD BE 30PSF
 ATTIC LIVE LOAD NOT 30PSF DEAD LOAD.
 REVISE AS REQ'D. TABLE 1604.1 FBC 2001.
  
 B) WINDOW GLAZING NOTE: REFERENCED SEC.
 #3513 DOESN'T APPLY. REVISE AS REQUIRED.
  
 5- SLIDING GLASS DOOR POCKET DETAIL.
 PREVIOUS CHECKLIST REQUIRED TO SPECIFY
 7/8" MIN. STUCCO THICKNESS AS REQUIRED
 BY ASTM C-926. DETAIL WAS REVISED TO
 HAVE 7/8" CDX PLYWOOD INSTEAD. REVISE AS
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.