Plan Review Notes
Plan Review Notes For Permit 05031189
Permit Number 05031189
Review Stop B
Sequence Number 2
Notes
Date Text
2005-06-27 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- SHEET A3: ROOF LOADS CHART WAS NOT
 REVISED. NEED TO SHOW THE 30PSF ATTIC
 LIVE LOAD AT GARAGE STORAGE AREA AND THE
 10PSF ATTIC LIVE LOAD AT NON STORAGE
 AREAS AS REQ'D BY TABLE 1604.1 FBC 2001.
  
 3- REAR ELEVATION STILL SHOWS BUTT
 GLAZING SYSTEM AT BREAKFAST AREA, MASTER
 BEDROOM AND LIVING ROOM. FLOOR PLAN
 CALLS FOR FIXED WINDOW. REVISE AS
 REQUIRED.
  
 4- SHEET A1: A) NOTE ON GARAGE ATTIC
 STORAGE IS WRONG. IT SHOULD BE 30PSF
 ATTIC LIVE LOAD NOT 30PSF DEAD LOAD.
 REVISE AS REQUIRED. 1604.1 FBC 2001.
  
 B) WINDOW GLAZING NOTE: WHERE IS SECTION
 #3513 TAKEN FROM?. IT DOESN'T APPLY.
 REVISE AS REQUIRED.
  
 5- SHEET A7: A) WOOD BEARING WALL DETAIL
 NEEDS MORE INFORMATION. SPECIFY
 HURRICANE CLIPS FOR TOP & BOTTOM STUDS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 B) SLIDING GLASS DOOR POCKET DETAIL
 NEEDS TO BE SPECIFIC WITH TYPE OF
 HURRICANE CLIPS TO BE USED AT BOTTOM AND
 TOP OF FRAMED WALL. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 **ALSO, SPECIFY 7/8" MIN. STUCCO
 THICKNESS AT FRAMED WALL AS REQUIRED BY
 ASTM C-926.
  
 6- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) 10'-0" HIGH ENTRY DOORS.
 B) POCKET SLIDING GLASS DOORS. SEE PLAN.
 C) WINDOW MULLIONS AND CLEARLY MARK SIZE
 & ANCHORS TO BE USED TO VERIFY DESIGN
 PRESSURES CAPACITY.
 D) CASEMENT WINDOWS. SEE PLANS.
 E) ALL TRUSS CONNECTORS SPECIFIED ON
 PLANS.
 F) MASTER BEDROOM, BREAKFAST AREA AND
 LIVING ROOM WINDOW ASSEMBLIES AS SHOWN
 ON PLANS.
 G) FIXED WINDOWS WITH SIZES A SHOWN ON
 FAMILY ROOM REAR FIXED WIND, ABOVE
 SLIDING GLASS DOOR AND BREAKFAST AREA.
 PRODUCT APPROVAL SUBMITTED DOESN'T COVER
 THOSE SIZES.
  
 7- WALL SECTION A/2 IS MISSING SPECS FOR
 CONNECTORS AT BOTTOM OF WOOD FRAMED
 WALL. SEC. 104.2.1.2 CITY ADMENDMENT TO
 FBC 2001.
  
 8- OWES $4247.67 FOR PERMIT FEES AND
 RADON FEES.
  
 9- ENERGY CALCULATIONS:
 A) OVERHANG LENGTH AND HEIGHT ARE STILL
 WRONG. SEE PLANS AND CHAPTER 13 FBC 2001
 FOR PROPER WAY TO CALCULATE THEM.
  
 B) ENERGY CALCS PREPARER TO SIGN AND
 DATE FORM.
  
 C) OWNER/AGENT TO SIGN AND DATE FORM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  