Plan Review Notes
Plan Review Notes For Permit 05031189
Permit Number 05031189
Review Stop B
Sequence Number 1
Notes
Date Text
2005-04-22 00:00:00BUILDING REVIEW CHECKLIST:
 1- PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3- SHEET A1: A) ATTIC ABOVE GARAGE USED
 FOR STORAGE NEEDS TO BE DESIGNED FOR
 30PSF LIVE LOAD AT BOTTOM CHORD OF
 TRUSS. ALSO, CLEARLY IDENTIFY AREAS
 DESIGNED FOR STORAGE. SPECIFY 10PSF OR
 30PSF ATTIC LIVE LOAD AS REQUIRED BY
 TABLE 1604.1 FBC 2001.
  
 B) SPECIFY SAFETY GLASS AT FAMILY ROOM
 AND MASTER BEDROOM WINDOWS AS REQUIRED
 BY SEC. 2405.2.1(3) FBC 2001.
  
 C) SPECIFY SIZE OF ATTIC ACCESS IN
 MASTER BEDROOM CLOSET. SEC. 2309.6 FBC.
  
 D) REVISE BEAM ELEVATION AT ENTRY DOORS.
 SEE SIZE OF DOOR.
  
 E) SHOW ON PLAN PRIVACY WALL SHOWN ON
 FOUNDATION PLAN.
  
 4- SHEET A2: A) PROVIDE FOOTINGS AND
 SPECS FOR PORTICO COLUMNS AND COLUMNS IN
 FRONT OF GARAGE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 B) SPECIFY WHY FOOTINGS FOR CONCRETE
 PIERS AT LOW PRIVACY WALL ARE BIGGER
 THAN FOOTINGS FOR INTERIOR BEARING
 COLUMN AND REAR PORCH COLUMN. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 5- SHEET A3: A) CLEARLY INDICATE ON ROOF
 FRAMING PLAN ANCHORS TO BE USED. SPECIFY
 ANCHOR AT ALL CONNECTIONS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 B) CONNECTOR SPECIFIED AT FRONT OF
 PORTICO IS FOR MASONRY APPLICATION.
 NEEDS WOOD TO WOOD CONNECTOR. SEE PLANS
 AND REVISE AS REQUIRED.
  
 C) REVISE ROOF LOADS CHART. NEED TO
 SPECIFY 30PSF AND 10PSF ATTIC LIVE LOADS
 IN ATTIC. TABLE 1604.1 FBC 2001.
  
 6- ELEVATIONS ON SHEET A6 DON'T MATCH
 FLOOR PLAN. RIGHT SIDE ELEVATIONS DON'T
 SHOW POCKET SLIDING GLASS DOORS AND
 GLASS BLOCK AS SHOWN ON PLANS. REAR
 ELEVATION DON'T SHOW SAME TYPE AND
 NUMBER OF WINDOW PANELS AS SHOWN ON
 PLANS. CLARIFY IF USING BUTT GLAZING OR
 BAY WINDOW ASSEMBLY.
  
 7- SHEET A7; REVISE CONNECTOR SPECIFIED
 ON WOOD BEARING WALL DETAIL. SEMCO IS
 OUT OF BUSINESS.
  
 8- PROVIDE FRAMING DETAILS AND SPECS FOR
 POCKET WALL FOR SLIDING GLASS DOOR. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 9- PROVIDE BBQ LISTING AND SPECS. NEED
 MANUFACTURER'S SPECS STATING THAT BBQ IS
 DESIGNED TO BE INSTALLED IN PORCH. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 10- CLEARLY SPECIFY IF USING IMPACT
 GLAZING OR STORM SHUTTERS AND PROVIDE
 COMPLETE INFORMATION FOR EITHER METHOD
 OF GLASS PROTECTION.
  
 11- PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL FOR: A) 10'-0" ENTRY
 DOORS.
  
 B) 18'-0" WIDE GARAGE DOOR.
  
 C) POCKET SLIDING GLASS DOORS. SEE PLANS
  
 D) WINDOW MULLIONS.
  
 E) CASEMENT WINDOWS.
  
 F) ALL TRUSS CONNECTORS SPECIFIED ON
 PLANS.
  
 G) HORIZONTAL SLIDER WINDOWS.
  
 H) BUTT GLAZING SYSTEM OR WINDOW
 ASSEMBLY AS SHOWN ON PLANS AT MASTER
 BEDROOM, LIVING ROOM AND BREAKFAST AREA.
  
 I) FRENCH DOORS AS SHOWN ON PLANS.
  
 12- PROVIDE FRAMING DETAILS & SPECS FOR
 WALL ABOVE BREAKFAST WINDOW. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 13- OWES $4247.67 FOR FERMIT FEES AND
 RADON FEES.
  
 14- ENERGY CALCULATIONS: A) NEED WORST
 CASE SCENARIO CALCULATIONS OR CALCS
 SHALL BE DONE WITH BUILDING CORRECT
 ORIENTATION.
  
 B) OVERHANG LENGHT AND HEIGHT ARE
 INCORRECT. SEE CHAPTER 13 FBC 2001 FOR
 PROPER WAY OF CALCULATING THESE
 DIMENSIONS AND REVISE AS REQUIRED.
  
 C) OWNER/AGENTTO SIGN AND DATE FORM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.