2005-04-22 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- PAY IMPACT FEES. BRING BACK STAMPED |
| DRAWINGS AND PAID RECEIPT. |
| |
| 2- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 3- SHEET A1: A) ATTIC ABOVE GARAGE USED |
| FOR STORAGE NEEDS TO BE DESIGNED FOR |
| 30PSF LIVE LOAD AT BOTTOM CHORD OF |
| TRUSS. ALSO, CLEARLY IDENTIFY AREAS |
| DESIGNED FOR STORAGE. SPECIFY 10PSF OR |
| 30PSF ATTIC LIVE LOAD AS REQUIRED BY |
| TABLE 1604.1 FBC 2001. |
| |
| B) SPECIFY SAFETY GLASS AT FAMILY ROOM |
| AND MASTER BEDROOM WINDOWS AS REQUIRED |
| BY SEC. 2405.2.1(3) FBC 2001. |
| |
| C) SPECIFY SIZE OF ATTIC ACCESS IN |
| MASTER BEDROOM CLOSET. SEC. 2309.6 FBC. |
| |
| D) REVISE BEAM ELEVATION AT ENTRY DOORS. |
| SEE SIZE OF DOOR. |
| |
| E) SHOW ON PLAN PRIVACY WALL SHOWN ON |
| FOUNDATION PLAN. |
| |
| 4- SHEET A2: A) PROVIDE FOOTINGS AND |
| SPECS FOR PORTICO COLUMNS AND COLUMNS IN |
| FRONT OF GARAGE. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| B) SPECIFY WHY FOOTINGS FOR CONCRETE |
| PIERS AT LOW PRIVACY WALL ARE BIGGER |
| THAN FOOTINGS FOR INTERIOR BEARING |
| COLUMN AND REAR PORCH COLUMN. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 5- SHEET A3: A) CLEARLY INDICATE ON ROOF |
| FRAMING PLAN ANCHORS TO BE USED. SPECIFY |
| ANCHOR AT ALL CONNECTIONS. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| B) CONNECTOR SPECIFIED AT FRONT OF |
| PORTICO IS FOR MASONRY APPLICATION. |
| NEEDS WOOD TO WOOD CONNECTOR. SEE PLANS |
| AND REVISE AS REQUIRED. |
| |
| C) REVISE ROOF LOADS CHART. NEED TO |
| SPECIFY 30PSF AND 10PSF ATTIC LIVE LOADS |
| IN ATTIC. TABLE 1604.1 FBC 2001. |
| |
| 6- ELEVATIONS ON SHEET A6 DON'T MATCH |
| FLOOR PLAN. RIGHT SIDE ELEVATIONS DON'T |
| SHOW POCKET SLIDING GLASS DOORS AND |
| GLASS BLOCK AS SHOWN ON PLANS. REAR |
| ELEVATION DON'T SHOW SAME TYPE AND |
| NUMBER OF WINDOW PANELS AS SHOWN ON |
| PLANS. CLARIFY IF USING BUTT GLAZING OR |
| BAY WINDOW ASSEMBLY. |
| |
| 7- SHEET A7; REVISE CONNECTOR SPECIFIED |
| ON WOOD BEARING WALL DETAIL. SEMCO IS |
| OUT OF BUSINESS. |
| |
| 8- PROVIDE FRAMING DETAILS AND SPECS FOR |
| POCKET WALL FOR SLIDING GLASS DOOR. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 9- PROVIDE BBQ LISTING AND SPECS. NEED |
| MANUFACTURER'S SPECS STATING THAT BBQ IS |
| DESIGNED TO BE INSTALLED IN PORCH. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 10- CLEARLY SPECIFY IF USING IMPACT |
| GLAZING OR STORM SHUTTERS AND PROVIDE |
| COMPLETE INFORMATION FOR EITHER METHOD |
| OF GLASS PROTECTION. |
| |
| 11- PROVIDE COMPLETE FLORIDA OR LOCAL |
| PRODUCT APPROVAL FOR: A) 10'-0" ENTRY |
| DOORS. |
| |
| B) 18'-0" WIDE GARAGE DOOR. |
| |
| C) POCKET SLIDING GLASS DOORS. SEE PLANS |
| |
| D) WINDOW MULLIONS. |
| |
| E) CASEMENT WINDOWS. |
| |
| F) ALL TRUSS CONNECTORS SPECIFIED ON |
| PLANS. |
| |
| G) HORIZONTAL SLIDER WINDOWS. |
| |
| H) BUTT GLAZING SYSTEM OR WINDOW |
| ASSEMBLY AS SHOWN ON PLANS AT MASTER |
| BEDROOM, LIVING ROOM AND BREAKFAST AREA. |
| |
| I) FRENCH DOORS AS SHOWN ON PLANS. |
| |
| 12- PROVIDE FRAMING DETAILS & SPECS FOR |
| WALL ABOVE BREAKFAST WINDOW. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 13- OWES $4247.67 FOR FERMIT FEES AND |
| RADON FEES. |
| |
| 14- ENERGY CALCULATIONS: A) NEED WORST |
| CASE SCENARIO CALCULATIONS OR CALCS |
| SHALL BE DONE WITH BUILDING CORRECT |
| ORIENTATION. |
| |
| B) OVERHANG LENGHT AND HEIGHT ARE |
| INCORRECT. SEE CHAPTER 13 FBC 2001 FOR |
| PROPER WAY OF CALCULATING THESE |
| DIMENSIONS AND REVISE AS REQUIRED. |
| |
| C) OWNER/AGENTTO SIGN AND DATE FORM. |
| |