Plan Review Notes
Plan Review Notes For Permit 05031177
Permit Number 05031177
Review Stop P
Sequence Number 1
Notes
Date Text
2005-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT 3.1 LUNCH ROOM SINK SHALL COMPLY
 WITH 11-4.24 AND ALL SUBSECTIONS. SHOW:
 A) HEIGHT 11-4.24.2
 B) KNEE CLEARANCE 11-4.24.3
 C) SINK DEPTH 11-4.24.4
 D) CLEAR FLOOR SPACE 11-4.24.5 FORWARD
 APPROACH REQUIRED. MAXIMUM 19"
 UNDERNEATH THE SINK. NO CABINET DOORS
 ALLOWED.
 E) EXPOSED PIPES & SURFACES 11-4.24.6
 F) FAUCETS 11-4.24.7
 2) A DRINKING FAUCET IS REQUIRED PER
 TABLE 403.1.
 3) SHT M1 WATER ISOMETRIC. FULL OPEN
 VALVES ARE REQUIRED ON ALL WATER
 DOWN-FEED LINES. SECTION 606.1(4).
 4) SHT M1 PLUMBING NOTES #10, AIR
 CHAMBERS ARE NOT APPROVED. SECTION 604.9
 IF WATER HAMMER ARRESTORS ARE PROVIDED,
 THEY SHALL BE LOCATED NEAR THE FIXTURE
 IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING. PDI-WH 201.
  