Date |
Text |
2005-03-25 00:00:00 | ******* UNSAT ****** |
| |
| 1)NOTE: PLEASE CORRELATE RISER/ PANEL |
| SCHEDULE/ PLANS. |
| RISER DOES NOT INDICATE APANEL "A", |
| HOWEVER SHOWS A PANEL "B"?? |
| 215.5 |
| |
| 2)NOTE: PLEASE SEE PLANS INDICATE AN |
| EXSITING COND UNIT, HOWEVER PANEL |
| SCHEDULE INDICATES A NEW COND UNIT? |
| |
| 3)NOTE: PLEASE CLARIFY NEW OR EXISTING |
| GFI REQUIRED FOR COND UNITS. 210.63 |
| PANEL SCHEDULE INDICATES AND EXSITNG |
| ROOFTOP RECEPT. |
| |
| 4)NOTE: PLEASE SHOW ALL DISC'S REQUIRED |
| FOR AHU'S , CU'S. 440.11 |
| |
| 5)NOTE: PLEASE SEE MISSING "SHOW WINDOW" |
| RECEPTS ON PLANS. PANEL SCHEDULE |
| INDICATES "SHOW WINDOW" RECEPTS, HOWEVER |
| THESE CIRCUITS ARE SHOWN GOING TO A |
| POWER POLE LOCATED IN THE CENTER OF THE |
| SHOWROOM. |
| PLEASE SEE 210.62, 220.12, NO OTHER |
| LOADS ARE PERMITTED ON SHOW WINDOW |
| CIRCUIT, PLEASE ALSO SEE 200 VA PER FT. |
| |
| 6)NOTE: PLEASE VERIFY #3 EQUIPMENT |
| GROUNDING CONDUCTOR SHOWN FROM 175A MAIN |
| BRKR TO PANEL. THIS IS PERMITTED AND |
| ONLY A NOTE: |
| |
| PLEASE SEE OTHER POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO TWO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| THIS WILL HELP IN PROCESS TO EXPEDITE |
| PLANS FOR PERMITTING. |
| PLEASE SUBMIT ONE COPY OF ANY OLD SHEETS |
| FOR REFERENCE ONLY. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESTITATE TO CALL. |
| |