Plan Review Notes For Permit 05031177 |
Permit Number |
05031177 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-04-19 00:00:00 | | | BUILDING PLAN REVIEW | | PERMIT: 05031177 | | ADD: 1335 OKEECHOBEE RD | | CONT:BUTLER | | TEL:(561)832-9700 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1)TABLE 803.3 MINIMUM INTERIOR FINISH | | CLASSIFICATION; PROVIDE INFORMATION | | BASED ON INTERIOR FINISH REQUIREMENTS | | BASED ON OCCUPANCY | | | | 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | ITIONS, EXIT ENCLOSURES, AND FIRE | | RATED WALLS REQUIRED TO HAVE PROTECTED | | OPENINGS SHALL BE EFFECTIVELY AND | | PERMANETLY IDENTIFIED WITH SIGNS OR | | STENCILING IN A MANNER ACCEPTABLE TO THE | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | CEILING CEILING AND IN CONCEALED SPACES. | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | PROTECT ALL OPENINGS". | | | | 3) PROVIDE THE MINIMUM BUILDING | | CLASSIFICATION, 601.2.1 | | | | 4) 11-4.24.2 SINKS, HEIGHT. SINKS SHALL | | BE MOUNTED WITH THE COUNTER NO HIGHER | | THAN 34" ABOVE THE FINISH FLOOR. | | 11-4.24.3 KNEE CLEARENCE THAT IS AT | | LEAST 27" HIGH 30" WIDE, AND 19" DEEP | | SHALL BE PROVIDED UNDERNEATH SINKS. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | | | | | | | |
|