Plan Review Notes
Plan Review Notes For Permit 05031175
Permit Number 05031175
Review Stop B
Sequence Number 2
Notes
Date Text
2005-03-23 00:00:00CHECKLIST:
 1- FLAT ROOF SYSTEM FROM FIRESTONE
 BUILDING PRODUCTS CO. IS LIMITED BY
 GENERAL LIMITATION #9 FOR -45PSF AS THE
 MAX. DESIGN PRESSURE. SYSTEM CAN'T BE
 ENHANCED TO ALLOW FOR GREATER DESIGN
 PRESSURES AS REQUIRED AT PERIMETER AND
 CORNERS OF ROOF. SEE TABLE 1606.2B
 FLORIDA BUILDING CODE 2001.
 NEED ANOTHER FLAT ROOF SYSTEM THAT CAN
 BE ENHANCED TO RESIST HIGHER UPLIFT
 REQUIREMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.