Plan Review Notes For Permit 05031157
Permit Number 05031157
Review Stop P
Sequence Number 1
Notes
Date Text
2005-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) MORE INFORMATION FOR ROOF DRAINAGE IS
 REQUIRED. SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 THE SQUARE FOOTAGE OF THE ROOF AND SHOW
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS. INDICAT SQUARE FOOTAGE TO BE
 DRAINING INTO THE PRIMARY ROOF DRAIN.
 ONLY ONE ROOF DRAIN SHOWN. SHOW THE SIZE
 OF THE NEW OVERFLOW SCUPPER AND
 DOWNSPOUT. SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS AND TABLES.
  
  
 REVIEW BY KEN STEVENS