2005-06-30 00:00:00DENIED:
 REFERENCE 2001 FBC(M)601.4, BALANCED
 RETURN AIR REQUIRED.PLAN INDICATES
 RETURN AIR THROUGH UNDERCUT DOOR, PLEASE
 NOTE IN THE EXCEPTION #1 & 2 A 1" DOOR
 UNDERCUT IS REQUIRED ALONG WITH A RETURN
 AIR JUMPER OR TRANSFER GRILLE.
  
 PLEASE SHOW COMPLIANCE.
  