Plan Review Notes For Permit 05031134 |
Permit Number |
05031134 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-05-17 00:00:00 | ******* PLANS REDLINED *********** | | | | PLEASE SEE NOTE #2 FROM PREVIOUS REVIEW | | INDICATED MISSING MCB REQUIRED ON | | SECONDARY SIDE OF TRANSFORMER. PLEASE | | SEE RESPONSE LETTER FROM ARCH INDICATES | | TO SEE REVISED ELECTRICAL RISER DIAGRAM, | | HOWEVER RISER WAS NOT REVISED TO INCLUDE | | THE REQUIRED MCB IN PANEL IL5. | | THIS HAS BEEN REDLINED ON PLANS FOR A | | MCB TO BE INSTALLED AS REQUIRED 408.16 | | ETC. | | | | PLANS NOW SIGNED WITH SIGNATURE FROM | | ARCHITECT. | | | | ELECTRICAL PLANS STAMPED. |
|