Plan Review Notes
Plan Review Notes For Permit 05031079
Permit Number 05031079
Review Stop E
Sequence Number 1
Notes
Date Text
2005-04-15 00:00:00 
 THE SELETED LOADS (PANELS A,E&C)EXCEED
 THE OUTPUT OF THE GENERATOR.
 PLEASE INDICATE SELECTED LOADS THAT ARE
 IN ACCEPTABLE LIMITS. SEE ARTICLE 702,
 702.5.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  