Plan Review Notes For Permit 05031079 |
Permit Number |
05031079 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-04-15 00:00:00 | | | THE SELETED LOADS (PANELS A,E&C)EXCEED | | THE OUTPUT OF THE GENERATOR. | | PLEASE INDICATE SELECTED LOADS THAT ARE | | IN ACCEPTABLE LIMITS. SEE ARTICLE 702, | | 702.5. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|