Plan Review Notes For Permit 05030993 |
Permit Number |
05030993 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-03-26 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) APPLICATION DOES NOT MENTION | | REPLACING THE DECK THAT WILL BE CUT UP | | FOR THE PIPING WORK. PLEASE INDICATE IF | | A SEPARATE PERMIT WILL BE APPLIED FOR TO | | REPLACE THE DECK. - IF THE DECK IS TO BE | | REPLACED ON THIS PERMIT, THAN THE VALUE | | OF THE JOB IS NOT CORRECT. SUBMIT A | | SIGNED & DATED COPY OF THE CONTRACT, AND | | THE WORK WILL BE CHECKED OUT BY MARSHALL | | AND SWIFT AS PER SECTIO 104.6.5. | | 2) FBC-2001 424.2.12.1 PRESSURE TESTS. | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | 3) FBC-2001 424.2.13.2 JOINTS AND | | CONNEDTIONS, FBC PLUMBING SECTION 605.21 | | PURPLE PRIMER REQUIRED ON PVC PIPING AND | | FITTINGS. (ADD TO NOTES) | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|