Notes
Date Text
2005-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) APPLICATION DOES NOT MENTION
 REPLACING THE DECK THAT WILL BE CUT UP
 FOR THE PIPING WORK. PLEASE INDICATE IF
 A SEPARATE PERMIT WILL BE APPLIED FOR TO
 REPLACE THE DECK. - IF THE DECK IS TO BE
 REPLACED ON THIS PERMIT, THAN THE VALUE
 OF THE JOB IS NOT CORRECT. SUBMIT A
 SIGNED & DATED COPY OF THE CONTRACT, AND
 THE WORK WILL BE CHECKED OUT BY MARSHALL
 AND SWIFT AS PER SECTIO 104.6.5.
 2) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 3) FBC-2001 424.2.13.2 JOINTS AND
 CONNEDTIONS, FBC PLUMBING SECTION 605.21
 PURPLE PRIMER REQUIRED ON PVC PIPING AND
 FITTINGS. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS