Plan Review Notes
Plan Review Notes For Permit 05030925
Permit Number 05030925
Review Stop G
Sequence Number 1
Notes
Date Text
2005-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) GENERATOR PERMIT IS REQUIRED FROM THE
 GENERAL CONTRACTOR WITH PLAN REVIEWS
 FROM BUILDING, ELECTRICAL, ZONING, AND
 MECHANICAL.
 2) GRILL IS NOT INDICATED ON THE
 APPLICATION.
 3) PROPANE TANK HOLDOWN DETAILS HAVE A
 ENGINEERING COMPANY TITLE BLOCK. EITHER
 THE ENGINEER SHALL SIGN/SEAL/DATE THE
 DETAIL, AND ALL LICENSES ECT REQUIRED BY
 FAC 61G15-23.002(1)(2) & FS 471.205 OR
 THE TITLE BLOCK SHALL BE REMOVED.
 HOLDDOWN DETAIL INDICATES GALVANIZED
 STEEL CABLES ON TANK. THESE CABLES SHALL
 BE ISOLATED FROM THE TANK TO PREVENT
 REMOVAL OF PROTECTION COATING. PLEASE
 INDICATE ON DETAIL METHOD OF ISOLATING
 THE CABLES FROM THE TANK, SECTION
 104.2.1.
 4) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS, AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 SECTION 104.2.1.
 5. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). - NO BTU LOAD FOR THE GENERATOR
 IS GIVEN, AND NO TOTAL BTU LOAD.
  