2005-03-26 00:00:00 | DENIED |
| REFERENCE: FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1) GENERATOR PERMIT IS REQUIRED FROM THE |
| GENERAL CONTRACTOR WITH PLAN REVIEWS |
| FROM BUILDING, ELECTRICAL, ZONING, AND |
| MECHANICAL. |
| 2) GRILL IS NOT INDICATED ON THE |
| APPLICATION. |
| 3) PROPANE TANK HOLDOWN DETAILS HAVE A |
| ENGINEERING COMPANY TITLE BLOCK. EITHER |
| THE ENGINEER SHALL SIGN/SEAL/DATE THE |
| DETAIL, AND ALL LICENSES ECT REQUIRED BY |
| FAC 61G15-23.002(1)(2) & FS 471.205 OR |
| THE TITLE BLOCK SHALL BE REMOVED. |
| HOLDDOWN DETAIL INDICATES GALVANIZED |
| STEEL CABLES ON TANK. THESE CABLES SHALL |
| BE ISOLATED FROM THE TANK TO PREVENT |
| REMOVAL OF PROTECTION COATING. PLEASE |
| INDICATE ON DETAIL METHOD OF ISOLATING |
| THE CABLES FROM THE TANK, SECTION |
| 104.2.1. |
| 4) ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS, AND ACCOMPANYING DATA |
| SHALL BEAR THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN. |
| SECTION 104.2.1. |
| 5. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). - NO BTU LOAD FOR THE GENERATOR |
| IS GIVEN, AND NO TOTAL BTU LOAD. |
| |