2005-04-12 00:00:00DENIED:
 PLAN SHEET M1 INDICATES THE SUPPLY
 DIFFUSER WILL BE DIRECTED AWAY FROM THE
 SMOKE DETECTOR.IN ACCORDANCE WITH NFPA
 72 AND NFPA 101, SMOKE DETECTORS ARE TO
 BE INSTALLED IN ACCORDANCE TO THE
 MANUFACTURERS SPECIFICATIONS AND NOT
 LOCATED WITHIN 3 FT OF THE SUPPLY AND 5
 FT FROM A RETURN.SMOKE DETECTOR
 SPACINGSHALL BE BASED ON TABLE
 2-3.6.6.2.
  