Plan Review Notes For Permit 05030813 |
Permit Number |
05030813 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-04-12 00:00:00 | DENIED: | | PLAN SHEET M1 INDICATES THE SUPPLY | | DIFFUSER WILL BE DIRECTED AWAY FROM THE | | SMOKE DETECTOR.IN ACCORDANCE WITH NFPA | | 72 AND NFPA 101, SMOKE DETECTORS ARE TO | | BE INSTALLED IN ACCORDANCE TO THE | | MANUFACTURERS SPECIFICATIONS AND NOT | | LOCATED WITHIN 3 FT OF THE SUPPLY AND 5 | | FT FROM A RETURN.SMOKE DETECTOR | | SPACINGSHALL BE BASED ON TABLE | | 2-3.6.6.2. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|