Plan Review Notes For Permit 05030813 |
Permit Number |
05030813 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-04-05 00:00:00 | 1) ALL EXIT DOORS THAT LEAVE THE | | CORRIDOR ARE REQUIRED TO SWING IN THE | | DIRECTION OF TRAVEL. PLANS SHOW SOME OF | | THE EXIT DOORS SWINGING INTO THE | | CORRIDOR. | | | | 2) ILLUMINATED EXIT SIGNS ARE REQUIRED | | ABOVE EVERY DOOR THAT SERVES AS AN EXIT. | | | | 3) PLANS DON'T SHOW ANY EMERGENCY | | LIGHTING. PLEASE INDICATE THE LOCATIONS | | OF EMERGENCY LIGHTS. | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS | | ARE REQUIRED FOR FIRE ALARM AND FIRE | | SPRINKLER REMODELS. | | | | | | MIKE WENNERGREN, A/CAPTAIN | | WPBFR(561) 835-2910 OR 805-6722 |
|