Plan Review Notes
Plan Review Notes For Permit 05030626
Permit Number 05030626
Review Stop P
Sequence Number 3
Notes
Date Text
2005-08-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 A. FROM PREVIOUS REVIEW:
 1B) SHT PE.1 SANITARY RISER DIAGRAM, A
 FUNNEL FLOOR DARAIN IS NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. PER SECTIONS
 802.3 & 802.3.2 EITHER A FLOOR SINK OR A
 HUB DRAIN IS REQUIRED. RESPONSE NOTED,
 BUT THIS JURISDICTION DOES NOT APPROVE A
 FLOOR DRAIN AS AN INDIRECT WASTE
 RECEPTOR, AND THE CODE STATES "AN
 APPROVED WASTE RECEPTOR"
 2B) SHT PE.1 SANITARY RISER DIAGRAM. THE
 BREAK ROOM SINK SHALL NOT DRAIN THROUGH
 THE HORIZONTAL WET VENT OF THE BATHROOM
 FIXTURES. THE SINK SHALL DISCHARGE
 DOWNSTREAM OF THE BATHROOM FIXTURES.
 SECTION 909.1. RESPONSE NOTED, BUT
 SECTION 908.1 READS " AN INDIVIDUAL VENT
 IS PERMITTED TO VENT TWO TRAPS OR
 TRAPPED FIXTURES AS A COMMON VENT". AS
 THE FLOOR DRAIN HAS A TRAP, A SEPARATE
 STACK WITH A VENT IS REQUIRED FOR THE
 BREAK ROOM SINK.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  