Plan Review Notes For Permit 05030626 |
Permit Number |
05030626 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-08-12 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | A. FROM PREVIOUS REVIEW: | | 1B) SHT PE.1 SANITARY RISER DIAGRAM, A | | FUNNEL FLOOR DARAIN IS NOT AN APPROVED | | INDIRECT WASTE RECEPTOR. PER SECTIONS | | 802.3 & 802.3.2 EITHER A FLOOR SINK OR A | | HUB DRAIN IS REQUIRED. RESPONSE NOTED, | | BUT THIS JURISDICTION DOES NOT APPROVE A | | FLOOR DRAIN AS AN INDIRECT WASTE | | RECEPTOR, AND THE CODE STATES "AN | | APPROVED WASTE RECEPTOR" | | 2B) SHT PE.1 SANITARY RISER DIAGRAM. THE | | BREAK ROOM SINK SHALL NOT DRAIN THROUGH | | THE HORIZONTAL WET VENT OF THE BATHROOM | | FIXTURES. THE SINK SHALL DISCHARGE | | DOWNSTREAM OF THE BATHROOM FIXTURES. | | SECTION 909.1. RESPONSE NOTED, BUT | | SECTION 908.1 READS " AN INDIVIDUAL VENT | | IS PERMITTED TO VENT TWO TRAPS OR | | TRAPPED FIXTURES AS A COMMON VENT". AS | | THE FLOOR DRAIN HAS A TRAP, A SEPARATE | | STACK WITH A VENT IS REQUIRED FOR THE | | BREAK ROOM SINK. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|