Plan Review Notes
Plan Review Notes For Permit 05030626
Permit Number 05030626
Review Stop P
Sequence Number 2
Notes
Date Text
2005-06-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY CODE
  
 A. FROM PREVIOUS REVIEW:
  
 2) ALL ARCHITECTURAL SHEETS, THE PRINTED
 NAME AND CERTIFICATE OF AUTHORIZATION IS
 REQUIRED ON EACH SHEET PER FAC
 61G1-16.004(2) & (6) AND FS 481.219 &
 481.2055. - RESPONSE NOTED, BUT COMMENT
 NOT ADDRESSED.
 3) ALL SHEETS WITH CRAVEN THOMPSON &
 ASSOCIATES, (CIVIL), REQUIRE A
 CERTIFICATE OF AUTHORIZATION NUMBER IN
 THE TITLE BLOCK. FAC 61G15-23.002(2) &
 FS 471.025. - RESPONSE NOTED, BUT
 COMMENT NOT ADDRESSED.
 5) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. - RESPONSE NOTED AS "A
 BOTTLE OF WATER", BUT A BOTTLED WATER
 COOLER ARI-1010 COMPLIANT IS REQUIRED IF
 A DRINKING FOUNTAIN IS NOT INSTALLED.
 SUBMIT MANUF. SPECIFICATION SHEETS THE
 BOTTLED WATER COOLER. SECTION 410.1
 6) SHT A5.0 SHEET IS "NOT" SIGNED,
 SEALED, OR DATED AS REQUIRED BY FAC
 61G1-16.004(5) AND FS 481.2055. - NO
 RESPONSE BECAUSE I FORGOT TO ADD "NOT".
 7) SHT A6.0 DETAIL #1 PER THE BUILDING
 OFFICIAL NO CABINET DOORS ALLOWED IN THE
 CLEAR FLOOR SPACE), AND FAUCETS
 11-4.24.7. REQUIRED ON PLANS
 TO SHOW COMPLIANCE. - RESPONSE NOTED,
 BUT NOT ALL SECTIONS ADDRESSED.
 8) ALL FS SHEETS, A CERTIFICATE OF
 AUTHORIZATION IS REQUIRED ON THE TITLE
 BLOCK ON EACH SHEET. ALSO THE SEAL AND
 SIGNATURE SHALL BE DATED WHEN SEAL AND
 SIGNATURE ARE AFFIXED TO PLANS. FAC
 61G15-23.002(2) & FS 471.2055.RESPONSE
 NOTED, BUT IF THE ENGINEER WORKS FOR
 BLYMYER ENGINEERING INC. A CERTIFICATE
 OF AUTHORIZATION IS REQUIRED. IF THE
 ENGINEER DOES NOT WORK FOR BLYMER
 ENGINEERING INC., HE MUST LEGIBLY
 INDICATE HIS ADDRESS ON EACH SHEET.
 **************NEW COMMENTS**************
 1B. SHT P3.1 SANITARY RISER DIAGRAM. A
 FUNNEL FLOOR DRAIN IS NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. PER SECTIONS
 802.3, AND 802.3.2 EITHER A FLOOR SINK
 OR A HUB DRAIN IS REQUIRED.
 2B. SHT P3.1 SANITARY RISER DIAGRAM. THE
 BREAK ROOM SINK SHALL NOT DRAIN THROUGH
 THE HORIZONTAL WET VENT OF THE BATHROOM
 FIXTRUES. THE SINK SHALL DISCHARGE
 DOWNSTREAM OF THE BATHROOM FIXTURES.
 SECTION 909.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]