2005-06-04 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| CITY CODE |
| |
| A. FROM PREVIOUS REVIEW: |
| |
| 2) ALL ARCHITECTURAL SHEETS, THE PRINTED |
| NAME AND CERTIFICATE OF AUTHORIZATION IS |
| REQUIRED ON EACH SHEET PER FAC |
| 61G1-16.004(2) & (6) AND FS 481.219 & |
| 481.2055. - RESPONSE NOTED, BUT COMMENT |
| NOT ADDRESSED. |
| 3) ALL SHEETS WITH CRAVEN THOMPSON & |
| ASSOCIATES, (CIVIL), REQUIRE A |
| CERTIFICATE OF AUTHORIZATION NUMBER IN |
| THE TITLE BLOCK. FAC 61G15-23.002(2) & |
| FS 471.025. - RESPONSE NOTED, BUT |
| COMMENT NOT ADDRESSED. |
| 5) A DRINKING FOUNTAIN IS REQUIRED PER |
| TABLE 403.1. - RESPONSE NOTED AS "A |
| BOTTLE OF WATER", BUT A BOTTLED WATER |
| COOLER ARI-1010 COMPLIANT IS REQUIRED IF |
| A DRINKING FOUNTAIN IS NOT INSTALLED. |
| SUBMIT MANUF. SPECIFICATION SHEETS THE |
| BOTTLED WATER COOLER. SECTION 410.1 |
| 6) SHT A5.0 SHEET IS "NOT" SIGNED, |
| SEALED, OR DATED AS REQUIRED BY FAC |
| 61G1-16.004(5) AND FS 481.2055. - NO |
| RESPONSE BECAUSE I FORGOT TO ADD "NOT". |
| 7) SHT A6.0 DETAIL #1 PER THE BUILDING |
| OFFICIAL NO CABINET DOORS ALLOWED IN THE |
| CLEAR FLOOR SPACE), AND FAUCETS |
| 11-4.24.7. REQUIRED ON PLANS |
| TO SHOW COMPLIANCE. - RESPONSE NOTED, |
| BUT NOT ALL SECTIONS ADDRESSED. |
| 8) ALL FS SHEETS, A CERTIFICATE OF |
| AUTHORIZATION IS REQUIRED ON THE TITLE |
| BLOCK ON EACH SHEET. ALSO THE SEAL AND |
| SIGNATURE SHALL BE DATED WHEN SEAL AND |
| SIGNATURE ARE AFFIXED TO PLANS. FAC |
| 61G15-23.002(2) & FS 471.2055.RESPONSE |
| NOTED, BUT IF THE ENGINEER WORKS FOR |
| BLYMYER ENGINEERING INC. A CERTIFICATE |
| OF AUTHORIZATION IS REQUIRED. IF THE |
| ENGINEER DOES NOT WORK FOR BLYMER |
| ENGINEERING INC., HE MUST LEGIBLY |
| INDICATE HIS ADDRESS ON EACH SHEET. |
| **************NEW COMMENTS************** |
| 1B. SHT P3.1 SANITARY RISER DIAGRAM. A |
| FUNNEL FLOOR DRAIN IS NOT AN APPROVED |
| INDIRECT WASTE RECEPTOR. PER SECTIONS |
| 802.3, AND 802.3.2 EITHER A FLOOR SINK |
| OR A HUB DRAIN IS REQUIRED. |
| 2B. SHT P3.1 SANITARY RISER DIAGRAM. THE |
| BREAK ROOM SINK SHALL NOT DRAIN THROUGH |
| THE HORIZONTAL WET VENT OF THE BATHROOM |
| FIXTRUES. THE SINK SHALL DISCHARGE |
| DOWNSTREAM OF THE BATHROOM FIXTURES. |