2005-03-25 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| CITY CODE |
| |
| 1) SHT PRIOR TO SHT C-3, ALL INFORMATION |
| DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME |
| AND SIGNATURE OF THE PERSON RESPONSIBLE |
| FOR THE DESIGN. SECTION 104.2.1. |
| 2) ALL ARCHITECTURAL SHEETS, THE PRINTED |
| NAME AND CERTIFICATE OF AUTHORIZATION IS |
| REQUIRED ON EACH SHEET PER FAC |
| 61G1-16.004(2) & (6) AND FS 481.219 & |
| 481.2055. |
| 3) ALL SHEETS WITH CRAVEN THOMPSON & |
| ASSOCIATES, (CIVIL), REQUIRE A |
| CERTIFICATE OF AUTHORIZATION NUMBER IN |
| THE TITLE BLOCK. FAC 61G15-23.002(2) & |
| FS 471.025. |
| 4) SHT C-10 CALL FOR A SAND/OIL |
| INTECEPTOR. THIS SHALL BE SIZED BY |
| RONDEY COMPO, ENVIRONMENTAL COMPLIANCE. |
| WASTE ORDINANCE 2938-96. CONTACT MR. |
| COMPO AT (561) 837-4074 OR E-MAIL |
| ADDRESS [email protected]. |
| 5) A DRINKING FOUNTAIN IS REQUIRED PER |
| TABLE 403.1. |
| 6) SHT A5.0 SHEET IS SIGNED/SEALED/DATED |
| AS REQUIRED BY FAC 61G1-16.004(5) AND |
| FS 481.2055. |
| 7) SHT A6.0 DETAIL #1 SHOW THE HEIGHT |
| 11-4.24.2, KNEE CLEARANCE 11-4.24.3, |
| SINK DEPTH 11-4.24.4, CLEAR FLOOR SPACE |
| 11-4.24.5 (FORWARD APPROACH EXTENDING |
| MAXIMUM 19" UNDERNEATH THE SINK REQD, |
| AND PER THE BUILDING OFFICIAL NO CABINET |
| DOORS ALLOWED IN THE CLEAR FLOOR SPACE), |
| EXPOSED PIPES AND SURFACES 11-4.24.6, |
| AND FAUCETS 11-4.24.7. REQUIRED ON PLANS |
| TO SHOW COMPLIANCE. |
| 8) ALL FS SHEETS, A CERTIFICATE OF |
| AUTHORIZATION IS REQUIRED ON THE TITLE |
| BLOCK ON EACH SHEET. ALSO THE SEAL AND |
| SIGNATURE SHALL BE DATED WHEN SEAL AND |
| SIGNATURE ARE AFFIXED TO PLANS. FAC |
| 61G15-23.002(2) & FS 471.2055. |
| 9) SUBMIT A SANITARY RISER ISOMETRIC |
| THAT REFLECTS THE FLOOR PLAN. SHOW ALL |
| PIPE SIZES, REQUIRED TRAPS, VENTS, AND |
| CLEANOUTS. SECTION 104.3.1.1. |
| 10) SUBMIT A WATER RISER ISOMETRIC. SHOW |
| ALL PIPE SIZES, VALVES, REQUIRED WATER |
| HAMMER ARRESTORS LOCATED NEAR THE |
| FIXTURES IN AN "EFFECTIVE RANGE" PER |
| PDI-WH 201, REQUIRED BACKFLOWS ECT. |
| SECTION 104.2.1.1. |
| 11) WATER SUPPLY TO THE CAR WASH SHALL |
| HAVE AN RPZ BACKFLOW PROTECTION. SECTION |
| 608.13.2. |
| 12) SUBMIT A ROOF PLAN SHOWING ALL |
| PRIMARY AND SECONDARY ROOF DRAINS. |
| INDICATE THE SQUARE FOOTAGE OF THE ROOF |
| AND THE SQUARE FOOTAGE DRAINING INTO |
| EACH DRAIN. SUBMIT CALCULATIONS FOR |
| PRIMARY AND SECONDARY ROOF DRAINS. |
| INCLUDE 1/2 AREA OF ALL VERTICAL WALLS |
| INCLUDING PARAPETS IN CALCULATIONS. |
| SECTIONS 1106 & 1107 AND ALL SUBSECTIONS |
| SUBMIT A DETAIL FOR SCUPPERS IF USED FOR |
| SECONDARY ROOF DRAINS SHOWING HEIGHT & |
| WIDTH. SUBMIT STORM DRAIN ISOMETRIC AND |
| STORM RISER DIAGRAMS SHOWING ALL PIPE |
| SIZES AND SQUARE FOOTAGE AS IT |
| ACCUMULATES IN THE SYSTEM. SECTION |
| 104.2.1. |
| 13) PLANS ARE INCOMPLETE AT THIS REVIEW |
| AND MORE COMMENTS MAY BE ADD ON THE NEXT |
| REVIEW. SECTION 104.2.1. |
| |