Plan Review Notes
Plan Review Notes For Permit 05030626
Permit Number 05030626
Review Stop P
Sequence Number 1
Notes
Date Text
2005-03-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY CODE
  
 1) SHT PRIOR TO SHT C-3, ALL INFORMATION
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. SECTION 104.2.1.
 2) ALL ARCHITECTURAL SHEETS, THE PRINTED
 NAME AND CERTIFICATE OF AUTHORIZATION IS
 REQUIRED ON EACH SHEET PER FAC
 61G1-16.004(2) & (6) AND FS 481.219 &
 481.2055.
 3) ALL SHEETS WITH CRAVEN THOMPSON &
 ASSOCIATES, (CIVIL), REQUIRE A
 CERTIFICATE OF AUTHORIZATION NUMBER IN
 THE TITLE BLOCK. FAC 61G15-23.002(2) &
 FS 471.025.
 4) SHT C-10 CALL FOR A SAND/OIL
 INTECEPTOR. THIS SHALL BE SIZED BY
 RONDEY COMPO, ENVIRONMENTAL COMPLIANCE.
 WASTE ORDINANCE 2938-96. CONTACT MR.
 COMPO AT (561) 837-4074 OR E-MAIL
 ADDRESS [email protected].
 5) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1.
 6) SHT A5.0 SHEET IS SIGNED/SEALED/DATED
 AS REQUIRED BY FAC 61G1-16.004(5) AND
 FS 481.2055.
 7) SHT A6.0 DETAIL #1 SHOW THE HEIGHT
 11-4.24.2, KNEE CLEARANCE 11-4.24.3,
 SINK DEPTH 11-4.24.4, CLEAR FLOOR SPACE
 11-4.24.5 (FORWARD APPROACH EXTENDING
 MAXIMUM 19" UNDERNEATH THE SINK REQD,
 AND PER THE BUILDING OFFICIAL NO CABINET
 DOORS ALLOWED IN THE CLEAR FLOOR SPACE),
 EXPOSED PIPES AND SURFACES 11-4.24.6,
 AND FAUCETS 11-4.24.7. REQUIRED ON PLANS
 TO SHOW COMPLIANCE.
 8) ALL FS SHEETS, A CERTIFICATE OF
 AUTHORIZATION IS REQUIRED ON THE TITLE
 BLOCK ON EACH SHEET. ALSO THE SEAL AND
 SIGNATURE SHALL BE DATED WHEN SEAL AND
 SIGNATURE ARE AFFIXED TO PLANS. FAC
 61G15-23.002(2) & FS 471.2055.
 9) SUBMIT A SANITARY RISER ISOMETRIC
 THAT REFLECTS THE FLOOR PLAN. SHOW ALL
 PIPE SIZES, REQUIRED TRAPS, VENTS, AND
 CLEANOUTS. SECTION 104.3.1.1.
 10) SUBMIT A WATER RISER ISOMETRIC. SHOW
 ALL PIPE SIZES, VALVES, REQUIRED WATER
 HAMMER ARRESTORS LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" PER
 PDI-WH 201, REQUIRED BACKFLOWS ECT.
 SECTION 104.2.1.1.
 11) WATER SUPPLY TO THE CAR WASH SHALL
 HAVE AN RPZ BACKFLOW PROTECTION. SECTION
 608.13.2.
 12) SUBMIT A ROOF PLAN SHOWING ALL
 PRIMARY AND SECONDARY ROOF DRAINS.
 INDICATE THE SQUARE FOOTAGE OF THE ROOF
 AND THE SQUARE FOOTAGE DRAINING INTO
 EACH DRAIN. SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS.
 INCLUDE 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS IN CALCULATIONS.
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 SUBMIT A DETAIL FOR SCUPPERS IF USED FOR
 SECONDARY ROOF DRAINS SHOWING HEIGHT &
 WIDTH. SUBMIT STORM DRAIN ISOMETRIC AND
 STORM RISER DIAGRAMS SHOWING ALL PIPE
 SIZES AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. SECTION
 104.2.1.
 13) PLANS ARE INCOMPLETE AT THIS REVIEW
 AND MORE COMMENTS MAY BE ADD ON THE NEXT
 REVIEW. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS