Date |
Text |
2005-04-11 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 05030626 |
| ADD: 2505 BRISTOL DRIVE |
| CONT:PLAN REVIEW |
| TEL: (561)684-5449#209 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| DISCREPANCY BETWEEN THE VICINITY MAP |
| SHEET A0.1 INDICATING THE SITE AND THE |
| PLAT MAP. |
| |
| 2)PROVIDE NOC RECORDED WITH THE CLERK OF |
| COURT BEFORE A PERMIT CAN BE ISSUED. |
| ***NOTE, ONCE THE NOTICE OF COMMENCEMENT |
| IS RECORDED WORK MUST BE COMMENCED OR BE |
| RE-RECORDED.**** |
| |
| 3) THE STRUCTURAL PLANS S-4 INDICATE THE |
| USE OF MANUFACTURED METAL BUILDINGS, NO |
| DRAWINGS WERE SUPPLIED.PLANS ARE TO |
| INDICATE WIND ZONE AND DESIGN CRIERIA. |
| |
| 4)FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) ROLL UP DOORS |
| B) EXTERIOR SWING DOORS, SOLID & |
| LOUVERED |
| C) WINDOWS |
| D) STORM SHUTTERS |
| E) ROOFING ASSEMBLIES |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 5) INDICATE THE PRESSURES FOR THE |
| WINDOWS AND DOORS OF THE ENCLOSED |
| STURURE? |
| |
| 6) SEE SHEET A6.0 DETAIL# 1 BREAKROOM |
| ELEVATIONS INDICATE SECTION# 7 FOR |
| HEIGHT DETAILS.PLEASE MAKE CORRETIONS. |
| 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| BE MOUNTED WITH THE COUNTER NO HIGHER |
| THAN 34" ABOVE THE FINISH FLOOR. |
| 11-4.24.3 KNEE CLEARENCE THAT IS AT |
| LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| SHALL BE PROVIDED UNDERNEATH SINKS. |
| |
| 7) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, SHEET |
| A2.0 INDICATES FLOOR PLAN NOTES, PLANS |
| INDICATE VARIOUS NUMBERED DETAILS BUT NO |
| NOTES FOLLOW, EXAMPLE 2-4 OR 6-7? |
| |
| 8)MECH TABLE 403.4.2 PUBLIC SPACES, |
| TOLIET ROOMS/ 50 CFM/ WATER CLOSET |
| FOOTNOTE "B" EXHAUST REQUIRED & |
| RECIRCULATION OF AIR IS PROHIBITED. |
| |
| 9) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| WHERE THE BEARING CAPACITY OF THE SOIL |
| IS NOT DEFINITLY KNOWN OR IS IN QUESTION |
| THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| TO THE PERMISSIBLE SAFE BEARING |
| CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| CITY SHALL BE CERTIFIED BY A GEOTECH- |
| NICALREPORT FROM A DESIGN PROFESSIONAL |
| PROPERLY LICENSED IN THE STATE OF |
| FLORIDA. |
| |
| 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| |
| |
| |