2005-04-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05030626
 ADD: 2505 BRISTOL DRIVE
 CONT:PLAN REVIEW
 TEL: (561)684-5449#209
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY BETWEEN THE VICINITY MAP
 SHEET A0.1 INDICATING THE SITE AND THE
 PLAT MAP.
  
 2)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
 ***NOTE, ONCE THE NOTICE OF COMMENCEMENT
 IS RECORDED WORK MUST BE COMMENCED OR BE
 RE-RECORDED.****
  
 3) THE STRUCTURAL PLANS S-4 INDICATE THE
 USE OF MANUFACTURED METAL BUILDINGS, NO
 DRAWINGS WERE SUPPLIED.PLANS ARE TO
 INDICATE WIND ZONE AND DESIGN CRIERIA.
  
 4)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) ROLL UP DOORS
 B) EXTERIOR SWING DOORS, SOLID &
 LOUVERED
 C) WINDOWS
 D) STORM SHUTTERS
 E) ROOFING ASSEMBLIES
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) INDICATE THE PRESSURES FOR THE
 WINDOWS AND DOORS OF THE ENCLOSED
 STURURE?
  
 6) SEE SHEET A6.0 DETAIL# 1 BREAKROOM
 ELEVATIONS INDICATE SECTION# 7 FOR
 HEIGHT DETAILS.PLEASE MAKE CORRETIONS.
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 7) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, SHEET
 A2.0 INDICATES FLOOR PLAN NOTES, PLANS
 INDICATE VARIOUS NUMBERED DETAILS BUT NO
 NOTES FOLLOW, EXAMPLE 2-4 OR 6-7?
  
 8)MECH TABLE 403.4.2 PUBLIC SPACES,
 TOLIET ROOMS/ 50 CFM/ WATER CLOSET
 FOOTNOTE "B" EXHAUST REQUIRED &
 RECIRCULATION OF AIR IS PROHIBITED.
  
 9) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.