Plan Review Notes
Plan Review Notes For Permit 05030593
Permit Number 05030593
Review Stop B
Sequence Number 1
Notes
Date Text
2005-03-10 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 1606.2.5THE SUBMITTED FLAT ROOF
 PRODUCT APPROVAL NOA ONLY LISTS SYSTEMS
 WITH MAXIMUM DESIGN PRESSURE OF LESS
 THAN -89 PSF.ALSO, EACH SYSTEM CITES
 GENERAL LIMITATION #9 (SEE PAGES 6
 THROUGH 12 OF 13).GENERAL LIMITATION
 #9 PROHIBITS RATIONAL ANALYSIS OR
 EXTRAPOLATION TO ENHANCE THE ALLOWABLE
 UPLIFT PRESSURE AT PERIMETER AND CORNER
 AREAS BY REDUCING THE FASTENER SPACING
 IN THESE AREAS.SELECT AN ALTERNATIVE
 PRODUCT APPROVAL THAT DOES NOT CITE
 GENERAL LIMITATION #9.ALTERNATIVELY IF
 THE SELECTED PRODUCT APPROVAL DOES CITE
 GENERAL LIMITATION #9, IT MUST HAVE A
 MAXIMUM DESIGN PRESSURE THAT EXCEEDS THE
 PRESSURE IN ROOF ZONE 3 (TYPICALLY -89
 PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR
 LESS).
  
 2) THE FLAT ROOF PRODUCT APPROVAL SHEETS
 MUST BE MARKED, AS APPROPRIATE, TO
 IDENTIFY WHICH SYSTEM IS TO BE USED SO
 THAT THE MAXIMUM DESIGN PRESSURE CAN BE
 VERIFIED
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]