2005-03-10 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| 1) FBC 1606.2.5THE SUBMITTED FLAT ROOF |
| PRODUCT APPROVAL NOA ONLY LISTS SYSTEMS |
| WITH MAXIMUM DESIGN PRESSURE OF LESS |
| THAN -89 PSF.ALSO, EACH SYSTEM CITES |
| GENERAL LIMITATION #9 (SEE PAGES 6 |
| THROUGH 12 OF 13).GENERAL LIMITATION |
| #9 PROHIBITS RATIONAL ANALYSIS OR |
| EXTRAPOLATION TO ENHANCE THE ALLOWABLE |
| UPLIFT PRESSURE AT PERIMETER AND CORNER |
| AREAS BY REDUCING THE FASTENER SPACING |
| IN THESE AREAS.SELECT AN ALTERNATIVE |
| PRODUCT APPROVAL THAT DOES NOT CITE |
| GENERAL LIMITATION #9.ALTERNATIVELY IF |
| THE SELECTED PRODUCT APPROVAL DOES CITE |
| GENERAL LIMITATION #9, IT MUST HAVE A |
| MAXIMUM DESIGN PRESSURE THAT EXCEEDS THE |
| PRESSURE IN ROOF ZONE 3 (TYPICALLY -89 |
| PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR |
| LESS). |
| |
| 2) THE FLAT ROOF PRODUCT APPROVAL SHEETS |
| MUST BE MARKED, AS APPROPRIATE, TO |
| IDENTIFY WHICH SYSTEM IS TO BE USED SO |
| THAT THE MAXIMUM DESIGN PRESSURE CAN BE |
| VERIFIED |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |