Plan Review Notes
Plan Review Notes For Permit 05030554
Permit Number 05030554
Review Stop E
Sequence Number 6
Notes
Date Text
2005-09-08 00:00:00REDLINED PANEL SCHEDULE AND PLANS FOR
 CIRCUITING.
 PLEASE SEE 26/28 SHOWS A/C UNIT, HOWEVER
 PLANS INDICATES GEN RECEPTS?
 PLEASE SEE CIRCUITING FO REM/EXT LTS PER
 700.12E, SHALL BE WIRED TO LOCAL
 LIGHTING BRANCH CIRCUIT.
 REDLINED BOTH SETS, PANEL SCHEDULE ON
 PANEL AT FIELD TO BE VERIFIED FOR CODE
 COMPLAINCE AND CORRECT CIRCUITS.