Plan Review Notes
Plan Review Notes For Permit 05030554
Permit Number 05030554
Review Stop E
Sequence Number 5
Notes
Date Text
2005-09-04 00:00:00********* UNSAT ********
  
  
 1)NOTE: PLEASE SEE PLANS HAVE COME BACK
 IN CONTAINING A RAISED SEAL OVER A
 "PHOTO-COPIED "SIGNATURE FOR THE
 ARCHITECT OF RECORD. PLEASE SEE FS
 481.221, FAC 61G1-16.003 WHICH STAES THE
 SIGNATURE OF ARCHITECT MUST BE AN
 ORIGINAL SIGNATURE.
 PLEASE SEE ONE COPY OF PLANS SUBMITTED
 IS BEING RETAINEDAND MAY BE SUBMITTED
 FOR POSSIBLE REVIEW BY STATE BOARD OF
 ARCHITECTS.
  
 2)NOTE: PLEASE RE-CAD PLANS WITH ALL
 INFORMATION AS CHANGED FROM ORIGINAL
 PLANS. PLEASE SEE FBC 104.2.1, WHICH
 REQUIRES PLANS TO BE DONE IN A NEAT A
 DETAILED MANNER FOR LEGIBILITY.
 PLEASE BE SURE ALL CIRCUITING FOR NEW
 DEVICES AND EQUIPMENTIS SHOWN ON PLANS
 AND CORRELATES WITH THE SUBMITTED PANEL
 SCHEDULE.
 PLEASE ALSO REVISE LOAD CALCULATIONS PER
 NEC 220
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  