Plan Review Notes For Permit 05030554 |
Permit Number |
05030554 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2005-08-18 00:00:00 | ********* UNSAT *********** | | | | *** PLEASE SEE COMMENTS FROM PREVIOUS | | "PROVISO" WHICH WAS GIVEN IN JUNE 05. | | | | | | 1)NOTE: PLEASE SEE 240.4,310.16 FOR MIN | | SEC'S/FEEDERS FOR A 200A SERVICE. | | PLEASE SEE 2/0'S ARE NOT RATED FOR | | 200A'S. | | | | 2)NOTE: PLEASE CORRELATE RISER DIAGRAM | | FOR FEEDERS, OCP, CONDUIT ETC FOR X-RAY | | EQUIPMENT. | | 310.16, 240.4, 215.5 | | | | 3)NOTE: PLEASE SEE FS 481.221 AND FAC | | 61G1-16.003 REQUIRES THE SEAL OF | | ARCHITECT TO RAISED, CLEAR AND VISABLE | | WITH ALL INFORMATION AS SET-FORTH ON | | SAID SEAL. | | PLEASE SEE RAISED SEAL IS NOT READABLE. | | PLEASE ALSO SEE FS 481.221 ALSO REQUIRES | | ARCHITECT TO "DATE" PLANS WHEN SIGNING. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|