Plan Review Notes
Plan Review Notes For Permit 05030554
Permit Number 05030554
Review Stop E
Sequence Number 3
Notes
Date Text
2005-06-24 00:00:00********** PROVISO/REVISION *********
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULE FOR NEW X-RAY FEED.
 PLEASE SEE RISER SHOWS 2/0'S AND PANEL
 SCHEDULE SHOWS #4??
 215.5
  
 2)NOTE: PLEASE SEE UPGRADE FOR SERVICE
 TO 200A'S PER 310.16, RISER SHOWS 2/0'S
 AND 3/0'S ARE REQUIRED.
  
 PLEASE MAKE THE ABOVE CORRECTIONS AND
 SUBMIT REVISION FOR REVIEW AND STAMPING
 BEFORE ROUGH ELECTRICAL INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  