2005-06-03 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FLORIDA STATUTES |
| |
| FROM PREVIOUS REVIEW: |
| 2. SHT A2 PROCESSING UNIT MAY REQUIRED A |
| NEUTRALIZING TANK. CONTACT RODNEY COMPO, |
| ENVIRONMENTAL COMPLIANCE (561) 837-4074, |
| OR E-MAIL [email protected]. SUBMIT HIS |
| DETERMINATION WORKSHEET WITH PLANS WHEN |
| RESUBMITTING PLANS FOR REVIEW. |
| 5. SHT P1 WATER RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN, NOR DOES IT MEET |
| THE CODE REQUIREMENTS. SECTION 104.2.1. |
| B. SHOW REQUIRED WATER HAMMER ARRESTORS |
| INSTALLED PER PDI-WH 201 & MANUF. |
| INSTALLATION INSTRUCTIONS. |
| F. AIR CHAMBERS ARE NOT APPROVED. |
| SECTION 604.9. - DELETE FROM RISER. |
| 6. SHT P2 THE FOLLOWING INFORMATION FOR |
| THE ACCESSIBLE TOILET ROOM SHALL BE |
| SHOWN ON THE DETAIL SHT P2 AND THE FLOOR |
| PLAN: |
| A. CLEAR FLOOR SPACE 11-4.16.2 - W/C |
| B. CLEAR FLOOR SPACE 11-4.19.3 - LAV |
| 7. ALL DEVICES INTENDED TO SERVE SOME |
| SPECIAL FUNCTION SUCH AS PROCESSING, AND |
| THAT CONNECT TO THE WATER SUPPLY SYSTEM, |
| SHALL BE PROVIDED WITH PROTECTION |
| AGAINST BACKFLOW. SECTION 608.3 - PLEASE |
| PROVIDE METHOD OF PROTECTION. SECTION |
| 104.2.1. - RESPONSE NOTED, BUT PER |
| SECTION 608.15.1 OPENINGS AND OUTLETS |
| EQUIPPED FOR HOSE CONNECTION SHALL BE |
| PROTECTED BY MEANS OTHER THAN AN AIR |
| GAP. |
| ****************NEW COMMENTS************ |
| 1B. SHT P1 SANT. RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN, NOR DOES IT MEET |
| CODE REQUIREMENT. |
| A. ONLY SHOW FIXTURES THAT WILL BE ON |
| THE RISER DIAGRAM. |
| B. THE SINK AND PROCESSOR SHALL NOT |
| DRAIN THROUGH THE HORIZONTAL WET VENT |
| FOR THE BATHROOM FIXTURES. SECTION 909.1 |
| SEE RED LINE CORRECTIONS FOR THIS ON THE |
| RISER DIAGRAM AND THE FLOOR PLAN. |
| C. FIXTURE IS MISLABELED. NEW SINK IN |
| DARK ROOM LABELED AS EXISTING LAV. |
| D. WASH MACHINE IS NOT VENTED AND A |
| CLEANOUT 4' ABOVE THE FLOOR IS REQUIRED |
| AT WASH MACHINE. |
| 2B. SHT P1 WATER RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN, NOR DOES IT MEET |
| CODE REQUIREMENTS. |
| A. INDICATE WHERE THE HOT AND COLD |
| WATER LINES PAST THE LAST FIXTURES TO |
| THE LEFT AND RIGHT ARE CONNECTING TO? |
| SECTION 104.2.1. |
| B. THE WATER CLOSET IS NOT SHOWN ON THE |
| RISER DIAGRAM. |
| C. NEW SINK IN DARK ROOM LABELED AS |
| EXISTING LAV. |
| D. DELETE ALL AIR CHAMBERS, AND SHOW |
| WATER HAMMER ARRESTORS AT WASH MACHINE |
| AS REQUIRED IN SECTION 604.9. |
| |
| REVIEW BY KEN STEVENS |