Plan Review Notes
Plan Review Notes For Permit 05030554
Permit Number 05030554
Review Stop P
Sequence Number 2
Notes
Date Text
2005-06-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 2. SHT A2 PROCESSING UNIT MAY REQUIRED A
 NEUTRALIZING TANK. CONTACT RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE (561) 837-4074,
 OR E-MAIL [email protected]. SUBMIT HIS
 DETERMINATION WORKSHEET WITH PLANS WHEN
 RESUBMITTING PLANS FOR REVIEW.
 5. SHT P1 WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 THE CODE REQUIREMENTS. SECTION 104.2.1.
 B. SHOW REQUIRED WATER HAMMER ARRESTORS
 INSTALLED PER PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS.
 F. AIR CHAMBERS ARE NOT APPROVED.
 SECTION 604.9. - DELETE FROM RISER.
 6. SHT P2 THE FOLLOWING INFORMATION FOR
 THE ACCESSIBLE TOILET ROOM SHALL BE
 SHOWN ON THE DETAIL SHT P2 AND THE FLOOR
 PLAN:
 A. CLEAR FLOOR SPACE 11-4.16.2 - W/C
 B. CLEAR FLOOR SPACE 11-4.19.3 - LAV
 7. ALL DEVICES INTENDED TO SERVE SOME
 SPECIAL FUNCTION SUCH AS PROCESSING, AND
 THAT CONNECT TO THE WATER SUPPLY SYSTEM,
 SHALL BE PROVIDED WITH PROTECTION
 AGAINST BACKFLOW. SECTION 608.3 - PLEASE
 PROVIDE METHOD OF PROTECTION. SECTION
 104.2.1. - RESPONSE NOTED, BUT PER
 SECTION 608.15.1 OPENINGS AND OUTLETS
 EQUIPPED FOR HOSE CONNECTION SHALL BE
 PROTECTED BY MEANS OTHER THAN AN AIR
 GAP.
 ****************NEW COMMENTS************
 1B. SHT P1 SANT. RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENT.
 A. ONLY SHOW FIXTURES THAT WILL BE ON
 THE RISER DIAGRAM.
 B. THE SINK AND PROCESSOR SHALL NOT
 DRAIN THROUGH THE HORIZONTAL WET VENT
 FOR THE BATHROOM FIXTURES. SECTION 909.1
 SEE RED LINE CORRECTIONS FOR THIS ON THE
 RISER DIAGRAM AND THE FLOOR PLAN.
 C. FIXTURE IS MISLABELED. NEW SINK IN
 DARK ROOM LABELED AS EXISTING LAV.
 D. WASH MACHINE IS NOT VENTED AND A
 CLEANOUT 4' ABOVE THE FLOOR IS REQUIRED
 AT WASH MACHINE.
 2B. SHT P1 WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS.
 A. INDICATE WHERE THE HOT AND COLD
 WATER LINES PAST THE LAST FIXTURES TO
 THE LEFT AND RIGHT ARE CONNECTING TO?
 SECTION 104.2.1.
 B. THE WATER CLOSET IS NOT SHOWN ON THE
 RISER DIAGRAM.
 C. NEW SINK IN DARK ROOM LABELED AS
 EXISTING LAV.
 D. DELETE ALL AIR CHAMBERS, AND SHOW
 WATER HAMMER ARRESTORS AT WASH MACHINE
 AS REQUIRED IN SECTION 604.9.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]