Plan Review Notes
Plan Review Notes For Permit 05030554
Permit Number 05030554
Review Stop E
Sequence Number 2
Notes
Date Text
2005-04-26 00:00:00****** UNSAT 2ND REVIEW ********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1 NO, PLEASE SEE RISER
 STILL INDICATED AS EXISTING YET, ALSO
 SHOWS UPGRADE. PLEASE CLARIFY WHAT WORK
 IS BEING DONE TO SERVICE.
 PLEASE SEE MAIN BRKR DISCONNECT IS SHOWN
 FEEDING MLO PANEL AND ALSO SHOWS A TAP ?
 TO NEW 150A DISC?
 215.5,240.21,240.4,310.16 ETC.
  
 2)NOTE: NOTE #2 NO, PLEASE SEE PREVIOUS
 NOTES.
 PLEASE SEE NEW NOTES AT BOTTOM.
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE NO
 CIRCUITING SHOWN FOR NEW?
 PLEASE SEE ONLY NOTE ADDED FOR EM LTS.
  
 NEW NOTES:
  
 1)NOTE: PLEASE SEE A PANEL SCHEDULE WAS
 NOW SUBMITTED, HOWEVER NO LIGHTING IS
 CIRCUITED ON PLANS? NO LIGHTING IN LOAD
 CALCULATIONS ?
 PLEASE ALSO SEE NO LOAD CALCULATIONS
 WERE DONE FOR SERVICE MAIN, TENANT MAIN
 ETC.
 215.5
  
 2)NOTE: PLEASE SEE NEW 150A MAIN DOES
 NOT MEET 110.26 FOR MIN CLEARENCE AS
 SHOWN ON PLANS.
  
 3)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONAL.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 4)NOTE: PLEASE SEE ELECTRICAL NOTES
 MENTIONS THE SFBC, WE ARE UNDER THE 2001
 FBC.
 PLEASE ALSO SEE NOTE WHICH MENTIOSN
 BROWARD COUNTY,,,,, ETC.
  
 PLEASE SEE SOME OF THE ABOVE ITEMS ARE
 REDLINED ON PLANS AT LOCATIONS OF NOTES.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  