Plan Review Notes For Permit 05030554 |
Permit Number |
05030554 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-03-28 00:00:00 | DENIED | | | | 1) PLEASE BE ADVISED THAT ALL | | CONSTRUCTION, RENOVATION AND DEMOLITION | | SHALL COMPLY WITH NFPA 241. | | | | 2) NO EXIT SIGNS OR EMERGENCY LIGHTING | | CAN BE FOUND ON THE PLANS. PLEASE | | INDICATE HOW THE MEANS OF EGRESS WILL BE | | ACCOMPLISHED. | | | | 3) PLEASE BE ADVISED THAT 2A-10B-C FIRE | | EXTINGUISHERS MUST BE MOUNTED NOT TO | | EXCEED A TRAVEL DISTANCE OF 75 FEET. | | | | 4) PLEASE PROVIDE INFORMATION REGARDING | | THE INTERIOR FINISH CLASSIFICATION OF | | WALLS AND CEILINGS. | | | | 5) SEPARATE SHOP DRAWINGS AND PERMIT | | WILL BE REQUIRED FOR THE FIRE ALARM | | REMODEL IF APPLICABLE. | | | | | | MIKE WENNERGREN, A/CAPTAIN | | WPBFR(561) 835-2910 |
|