2005-03-14 00:00:00 | ************ UNSAT *************** |
| |
| 1)NOTE: PLEASE SEE SERVICE NOTE MENTIONS |
| |
| UPGRADE EXISTING ELECTRICAL RISER. |
| PLEASE VERIFY WHAT APPAEARS TO BE A |
| "TAP" FROM 200A MAIN DISC WHICH ALREADY |
| FEEDS AND EXISTING 200A MLO PANEL. |
| 240.21 |
| |
| 2)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS |
| FOR EXISTING 200A DISCONNECT AND FOR |
| EXSITNG 1200A MAIN SERVICE. |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE SEE ALL CONTINOUS LOADS TO BE |
| SHOWN AT 125%.215.3,230.42 ETC |
| 215.5 |
| |
| 3)NOTE: PLEASE SEE CONDUCTOR SIZE SHOWN |
| FROM 150A DISCONNETC. #1? |
| PLEASE SEE 310.16 75DEGREE COLUMN FOR |
| MIN AWG FOR 150A'S. |
| |
| 4)NOTE: PLEASE INCLUDE ALL CIRCUITNG ON |
| PLANS FOR NEW AND CORRELATE WITH A PANEL |
| SCHEDULE TO BE SUBMITTED. |
| PLEASE ALSO SEE 700.12E FOR CIRCUITING |
| OF ANY EM/EXT LTS WHICH MAY OR MAY NOT |
| BE REQUIRED. |
| |
| PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| PLEASE SUBMIT ONE COPY OF OLD SHEETS FOR |
| REFERENCE ONLY. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |