Plan Review Notes
Plan Review Notes For Permit 05030554
Permit Number 05030554
Review Stop B
Sequence Number 1
Notes
Date Text
2005-03-22 00:00:00PERMIT #05030554
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.) THE SEAL IS TO BE DATED, FAC61G1-15.
  
 3.) OCCUPANCY CLASSIFICATIONS OF B AND M
 (STATED AS ?RETAIL?) ARE DECLARED, SHEET
 A.PLEASE READ FBC CHAPTER 3.IF THERE
 ARE TWO OCCUPANCIES, PLEASE SHOW
 OCCUPANCY SEPARATION REQUIRED FBC TABLE
 704.1.
  
 4.) SHOW THE MANEUVERING CLEARANCE, PUSH
 SIDE, FOR THE NEW DOCTOR?S OFFICE, NEW
 TREATMENT ROOM #1,EXISTING KITCHEN
 PULL SIDE, ACCESSIBLE BATHROOM PULL
 SIDE, NEW TREATMENT ROOM #3 PUSH AND
 PULL SIDE.
  
 5.) THE ELEVATION FOR THE TOILET/LAV, P2
 DOES NOT MATCH THE FLOOR PLAN.NOTE
 MINIMUM DISTANCE FROM CENTERLINE OF
 TOILET TO LAV, FBC11 FIGURE 28.
  
 6.) ELEVATION, P2 SIDE WALL, SHOW MAX
 DISTANCE FOR GRAB BAR FROM THE BACK
 WALL, FBC11 FIGURE 29.
  
 7.) NOTE HALLWAY WIDTHS.
  
  