2005-03-28 00:00:00****** UNSAT *****
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING FROM MAIN TO MLO PANEL.
 250.110,250.24, 250.122
  
 2)NOTE: PLEASE SEE MISSING CWP AS PART
 OF THE GROUNDING ELECTRODE SYSTEM.
 250.50
  
 3)NOTE: PLEASE INCLUDE CONDUCOTRS TO NEW
 A/C EQUIPMENT/DISCS'.
  
 4)NOTE: PLEASE SEE FBC 104.2.1, WHICH
 REQUIRES THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN.
  
 5)NOTE: PLEASE ALSO SEE TWO SETS MIN
 REQUIRED FOR REVIEW AND STAMPING.
  
 6)NOTE: PLEASE PROVIDE A LAYOUT FOR
 ADDITIONAL ELECTRICAL WORK AS PROPOSED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  