2005-03-16 00:00:001) THE SAFETY MARGIN IS BELOW 5 PSI. PER
 THE CITY OF WEST PALM BEACH FIRE
 MARSHAL'S OFFICE, THE SAFETY MARGIN MUST
 BE 5 PSI OR GREATER.
  
 2) PLEASE SHOW THE LOCATION OF THE FIRE
 DEPARTMENT CONNECTION AND IT'S DISTANCE
 TO THE CLOSEST FIRE HYDRANT. THAT
 DISTANCE CAN BE NO FURTHER THAN 150'.
  
  
 MIKE WENNERGREN, ACTING CAPTAIN
 WPBFR(561) 835-2910