2005-03-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A1 DETAIL #6 FOLLOWING
 INFORMATION IS REQUIRED ON DETAIL:
 A) KNEE CLEARANCE 11-4.24.3 (HEIGHT)
 B) CLEAR FLOOR SPACE 11-4.24.5FORWARD
 APPROACH REQUIRED, MAX. 19" UNDERNEATH
 THE SINK. - PER BUILDING OFFICIAL, NO
 DOORS IN CLEAR FLOOR SPACE UNDER SINK.
 C) EXPOSED PIPES AND SURFACES 11-4.24.6
  
 2) PLEASE INDICATE IF DRINKING FOUNTAINS
 ARE AVAILABLE IN THE COMMON AREAS OF THE
 BUILDING.
  
 3) A FULL OPEN VALVE IS REQUIRED ON ALL
 WATER DOWN-FEED LINES. SECTION 606.1(4)
  
 4) SHOW WATER HAMMER ARRESTOR REQUIRED
 BY SECTION 604.9 ON WATER RISER DIAGRAM.
 SECTION 104.2.1.
  
  
 REVIEW BY KEN STEVENS