Notes |
Date |
Text |
2005-03-07 00:00:00 | ********* UNSAT ************ | | | | 1)NOTE: PLEASE SEE EACH SET SUBMITTED. | | ONE SET CONTAINS E1 OF 2 AND 2 OF 2, THE | | OTHER SET CONTAINS TWOE1 OF 2 SHEETS. | | | | 2)NOTE: PLEASE CORRELATE LABELING OF | | PANELS ON PANEL SCHEDULES AND RISER. | | HP, LP, H OR L? | | 215.5 | | | | 3)NOTE: PLEASE SEE THERE ARE NO | | CONDUCTORS SHOWN FROM PANEL H TO | | TRANSFORMER TO PANEL L. | | 310.16, 215.5 | | | | 4)NOTEP: PLEASE INCLUDE EQUIPMENT | | GROUNDING METHODS FOR ALL EQUIPMENT/ | | CONDUITS. | | 250.110/ 250.122 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|