Plan Review Notes For Permit 05030164 |
Permit Number |
05030164 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-03-14 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} CALCULATE AND SUBMIT THE AVAILABLE | | FAULT CURRENT AND INDICATE AIC RATING | | FOR THE SERVICE EQUIPMENT PER 110.9 & | | 10. | | | | 2} THE RISER DIAGRAM IS TO VAGUE. | | INDICATE WHAT IS TO BE INSTALLED ON THE | | PLAN. REMOVE ALL "OPTIONS" AND "IF | | REQUIRED" LANGUAGE. IF UNCERTAIN | | COORDINATE WITH ELECTRICAL CONTRACTOR. | | | | 3} INDICATE THE LOCATION OF ALL SERVICE | | EQUIPMENT ON THE PLAN PER 110.26, 215.5 | | AND 230.70 CWBP AMMENDMENTS. | | | | 4} INDICATE ALL COMPONENTS OF THE | | GROUNDING ELECTRODE SYSTEM PER 250.50. | | | | 5} CORRELATE THE MECHANICAL SPECS AND | | ELECTRICAL PANEL FOR EQUIPMENT SIZE. SEE | | AHU HEATER SIZE. | | | | 6} INDICATE COMPLIANCE OF 210.12 AFCI | | FOR SLEEPING ROOMS ON PANEL SCHEDULE. | | | | 7} THE ENGINEER OF RECORD MUST PROVIDE A | | TITLE BLOCK ON THE PLANS PER FAC | | 61G15-23.002. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|