Plan Review Notes
Plan Review Notes For Permit 05030164
Permit Number 05030164
Review Stop E
Sequence Number 1
Notes
Date Text
2005-03-14 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} CALCULATE AND SUBMIT THE AVAILABLE
 FAULT CURRENT AND INDICATE AIC RATING
 FOR THE SERVICE EQUIPMENT PER 110.9 &
 10.
  
 2} THE RISER DIAGRAM IS TO VAGUE.
 INDICATE WHAT IS TO BE INSTALLED ON THE
 PLAN. REMOVE ALL "OPTIONS" AND "IF
 REQUIRED" LANGUAGE. IF UNCERTAIN
 COORDINATE WITH ELECTRICAL CONTRACTOR.
  
 3} INDICATE THE LOCATION OF ALL SERVICE
 EQUIPMENT ON THE PLAN PER 110.26, 215.5
 AND 230.70 CWBP AMMENDMENTS.
  
 4} INDICATE ALL COMPONENTS OF THE
 GROUNDING ELECTRODE SYSTEM PER 250.50.
  
 5} CORRELATE THE MECHANICAL SPECS AND
 ELECTRICAL PANEL FOR EQUIPMENT SIZE. SEE
 AHU HEATER SIZE.
  
 6} INDICATE COMPLIANCE OF 210.12 AFCI
 FOR SLEEPING ROOMS ON PANEL SCHEDULE.
  
 7} THE ENGINEER OF RECORD MUST PROVIDE A
 TITLE BLOCK ON THE PLANS PER FAC
 61G15-23.002.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  