Plan Review Notes For Permit 05030158 |
Permit Number |
05030158 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-03-15 00:00:00 | ******** UNSAT ********* | | | | 1)NOTE: PLEASE SEE MISSING SD'S REQUIRED | | INSIDE AND OUTSIDE BEDRM. | | NFPA-72 8-1.4.1.6.2 | | | | 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | -ED PER 210.8A-6 | | SHOWN ON PLANS AS NEW? | | | | 3)NOTE: PLEASE SEE 210.12 2002 NEC FOR | | REQUIRED ARC FAULT PROTECTION IN | | BEDROOMS. | | SD'S, LTS, FANS, RECEPTS ETC ARE ALL TO | | BE AFCI PROTECTED. | | | | 4)NOTE: PLEASE SEE 220.31B FOR LOAD | | CALCUALTIONS FOR EXSITNG SERVICES. | | PLEASE VERIFY BOTH LOAD CALCULATIONS | | SHOWN. EXISTING AND NEW? | | PLEASE SEE WHAT APPEARS TO BE REVISED | | "NEW" LOAD CALCULATIONS INDICATES ONLY | | ONE AHU? PLANS APPEAR TO NOTE THAT THERE | | MAY BE MORE THAN ONE | | NOTE FOR LOAD CALCULATIONS MENTIONS ONLY | | LOAD ADDED AS 2.3 AMPS, HOWEVER LOAD | | CALCUALTIONS DO NOT CORRELATE WITH THIS. | | | | 5)NOTE: PLEASE SEE RECEPTS AT OUTSIDE | | LOCATIONS TO BE SHOWN AS GFI, 210.8. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | | | | | |
|