Plan Review Notes
Plan Review Notes For Permit 05030158
Permit Number 05030158
Review Stop E
Sequence Number 1
Notes
Date Text
2005-03-15 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SEE MISSING SD'S REQUIRED
 INSIDE AND OUTSIDE BEDRM.
 NFPA-72 8-1.4.1.6.2
  
 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 SHOWN ON PLANS AS NEW?
  
 3)NOTE: PLEASE SEE 210.12 2002 NEC FOR
 REQUIRED ARC FAULT PROTECTION IN
 BEDROOMS.
 SD'S, LTS, FANS, RECEPTS ETC ARE ALL TO
 BE AFCI PROTECTED.
  
 4)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCUALTIONS FOR EXSITNG SERVICES.
 PLEASE VERIFY BOTH LOAD CALCULATIONS
 SHOWN. EXISTING AND NEW?
 PLEASE SEE WHAT APPEARS TO BE REVISED
 "NEW" LOAD CALCULATIONS INDICATES ONLY
 ONE AHU? PLANS APPEAR TO NOTE THAT THERE
 MAY BE MORE THAN ONE
 NOTE FOR LOAD CALCULATIONS MENTIONS ONLY
 LOAD ADDED AS 2.3 AMPS, HOWEVER LOAD
 CALCUALTIONS DO NOT CORRELATE WITH THIS.
  
 5)NOTE: PLEASE SEE RECEPTS AT OUTSIDE
 LOCATIONS TO BE SHOWN AS GFI, 210.8.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  