Plan Review Notes For Permit 05030144 |
Permit Number |
05030144 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-03-21 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) AS REQUIRED BY 104.3.1.1 OF THE CODE, | | TWO OR MORE SETS OF DRAWINGS SHAL | | ACCOMPANY THE APPLICATION FOR A PERMIT. | | SECTION 104.2.1. - PLANS SHALL BE | | SUBMITTED IN SETS, NOT LOOSE SHEETS. | | 2) INDICATE FLUSH CONTROLS FOR W/C PER | | SECTION 11-4.16.5. SHT A-1 | | 3) SHOW COMPLIANCE WITH 11-4.19.7, | | FAUCETS FOR THE LAV. SHT A-1 | | 4) SUBMIT SANITARY AND WATER RISER | | DIAGRAMS. SHOW PIPE SIZE, VENTING AND | | POINT OF CONNECTION FOR THE SANT., AND | | SHOW PIPE SIZE, VALVES, LOCATION OF | | WATER HAMMER ARRESTORS, (IF INSTALLED | | PER PDI-WH 201), AND POINT OF | | CONNECTION. SECTION 104.3.1.1. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|