Date |
Text |
2006-12-27 17:46:31 | *** UNSAT ** |
| |
| 1) NOTE: PLEASE SUBMIT ONE COMPLETE SET OF |
| PHOTO-METRICS. PLEASE KNOW AS THIS IS REQUIRED UNDER |
| THE ELECTRICAL, LIFE SAFETY AND ELECTRICAL ENGINEER IS |
| ALSO RESPONSIBLE FOR THIS SCOPE OF WORK, ALL PLANS |
| SHALL BE DONE BY THE ENGINEER OF RECORD. FS 471.025 |
| PLEASE SEE SOME PHOTO-METRICS WERE DONE BY THE ENGINEER |
| HOWEVER THEY ARE NOT THE SAME AS THE OTHERS DONE WHICH |
| WERE NOT SIGNED, AND SEALED BY ANYONE. |
| PLEASE KNOW AS PER NFPA-101, 7.9, AND 7.8, 7.8.1.3, |
| 7.9.2.2, EMERGENCY LIGHTING IS REQUIRED OUT OF THE |
| BUILDING LEADING TO THE PUBLIC RIGHT OF WAY. PLEASE SEE |
| THIS WOULD INCLUDE STAIRS OUTSIDE. |
| PLEASE SEE ONE OF THE MOST IMPORTANT ITEMS WAS REMOVED |
| FROM PLANS WHICH WERE THE REQUIRED BATTERY BACK UP |
| FIXTURES FROM THE STAIRWAYS. PLEASE SEE THAT SOME SORT |
| OF BATTERY BACK UP FIXTURES WILL BE REQUIRED AS |
| REQUIRED AND SHOWN ON ORIGINAL PLANS. |
| |
| 2) NOTE: PLEASE SEE THE NEW PROPOSED SERVICE FOR THE |
| CHPP IS NOT YET APPROVED AS SHOWN. PLEASE SEE 230.2 |
| WHICH SPECIAL PERMISSION MUST FIRST BE GRANTED BY THE |
| AHJ IF THE BUILDING MEETS THE EXCEPTIONS TO INSTALL NEW |
| SERVICE. PLEASE KNOW AT THIS TIME THIS IS NOT |
| PERMITTED. |
| PLEASE SEE CHILLER PLANT STRUCTURE/AREA/BUILDING |
| CONTAINS A FEEDER FROM THE OTHER ELECTRICAL SERVICE |
| WHICH ISNOT PERMITTED AND/OR IF IT DOES COMES TO THE |
| POINT OF BEING PERMITTED, THEN A MEANS OF DISCONNECT |
| AND SIGNAGE AT THIS LOCATION FOR PANEL AUX WILL BE |
| REQUIRED AT A MINIMUM. |
| 225.31-225.39, 230.2E ETC. |
| |
| 3) NOTE: PLEASE SEE AS NOTED ABOVE IN NOTE #2, PLEASE |
| EXPLAIN AND INDICATE ANY CONTROL WIRING OR CONDUCTORS |
| OF ANY TYPE WHICH ARE BEING INSTALLED FROM THE NEW |
| PROPOSED CHILLER PLANT SERVICE WHICH WILL PROCEED INTO |
| THE MAIN COURTHOUSE BUILDING WHICH IS BEING FED FROM A |
| COMPLETELY DIFFERENT SERVICE AND SEPARATE FPL |
| TRANSFORMER. |
| PLEASE SEE MIXING OF SERVICES AND MEANS OF DISCONNECTS |
| REQUIRED FOR THESE CONDUCTORS OR CONTROL WIRING PER |
| 225.31-225.39. |
| PLEASE KNOW AS MUCH OF NOTES 2 AND 3 ARE NOT KNOWN AT |
| THIS TIME, THERE MAY BE COMMENTS WHICH WILL FOLLOW THIS |
| REVIEW. |
| |
| 4) NOTE: PLEASE SEE 240.4C WITH RESPECT TO THE MINIMUM |
| SIZE OF THE SERVICE ENTRANCE CONDUCTORS AS WELL AS THE |
| MINIMUM SIZE FOR FEEDERS FOR DEVICES RATED OVER 800A?S. |
| PLEASE SEE SECTIONS AS THESE SHALL BE SIZED AT OR ABOVE |
| THE MINIMUM RATING OF THE OVER CURRENT PROTECTION |
| DEVICE. PLEASE SEE 310.16, 110.14. |
| PLEASE CORRELATE AND ADJUST. |
| PLEASE SEE THIS IS FOR ALL DEVICES OVER 800A ARE, |
| INCLUDING ALL MAINS ON BUILDING. IF THE CONDUCTORS TO |
| MAINS ARE BY UTILITY COMPANY THIS WOULD NOT APPLY. |
| |
| 5) NOTE: PLEASE SUBMIT MANUFACTURE?S SPECS/CUT SHEETS |
| FOR THE NEW TANK LESS WATER HEATERS/INST-HOT UNITS. |
| 110.3, 90.7. |
| |
| |
| 6) NOTE: PLEASE SEE MISSING FOOTER STEEL FOR CHILLER |
| PLANT AREAS PER 250.32, 2500.50. |
| |
| 7) NOTE: PLEASE SEE THERE ARE SEVERAL AREAS ON PLANS |
| WHICH INDICATE A REV #3, ALTHOUGH NOTHING HAS CHANGED |
| FROM THE PREVIOUS/ORIGINAL SET OF PLANS WHICH CONTAIN |
| THE SAME ITEMS, WORDING ETC. |
| PLEASE SEE JUST TO NAME A FEW, NOTES ON RISER SHEETS |
| #3, NOTES #16-21 ETC. |
| RISER FOR MAINS? ETC |
| PLEASE EXPLAIN REVISION AND WHAT IS BEING REVISED SINCE |
| REVISION #2, AS PLANS ARE NOT CHANGED FROM FILE/RECORD |
| SET OF PLANS. |
| FBC 106.1.2 ADMIN SECTION. |
| |
| 8) NOTE: PLEASE SEE ALSO SEE NOTE ABOVE WITH RESPECT TO |
| LOCATION ON PLANS NOTED FOR REVISION #1, YET CHANGES |
| COULD NOT BE FOUND FROM RECORD SET OF PLANS? |
| |
| 9) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPEOF |
| WORK ON PROJECT NEEDS TO BE UPDATED AS THE SCOPE OF |
| WORK FOR MANY ITEMS HAS COMPLETELY CHANGED FROM APPLIED |
| AMOUNT. |
| PLEASE SEE PREVIOUS FBC ADMIN SECTION 106.3.5 OR |
| CURRENT CODE 108.3 BOTH OF WHICH STATE THE SAME |
| REQUIREMENTS. |
| THIS IS REQUIRED BEFORE ANY FURTHER REVISIONS ARE DONE |
| AND VALUE WILL BE REVIEWED FOR PROJECT. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |