Plan Review Notes
Plan Review Notes For Permit 05030119
Permit Number 05030119
Review Stop E
Sequence Number 9
Notes
Date Text
2006-12-27 17:46:31*** UNSAT **
  
 1) NOTE: PLEASE SUBMIT ONE COMPLETE SET OF
 PHOTO-METRICS. PLEASE KNOW AS THIS IS REQUIRED UNDER
 THE ELECTRICAL, LIFE SAFETY AND ELECTRICAL ENGINEER IS
 ALSO RESPONSIBLE FOR THIS SCOPE OF WORK, ALL PLANS
 SHALL BE DONE BY THE ENGINEER OF RECORD. FS 471.025
 PLEASE SEE SOME PHOTO-METRICS WERE DONE BY THE ENGINEER
 HOWEVER THEY ARE NOT THE SAME AS THE OTHERS DONE WHICH
 WERE NOT SIGNED, AND SEALED BY ANYONE.
 PLEASE KNOW AS PER NFPA-101, 7.9, AND 7.8, 7.8.1.3,
 7.9.2.2, EMERGENCY LIGHTING IS REQUIRED OUT OF THE
 BUILDING LEADING TO THE PUBLIC RIGHT OF WAY. PLEASE SEE
 THIS WOULD INCLUDE STAIRS OUTSIDE.
 PLEASE SEE ONE OF THE MOST IMPORTANT ITEMS WAS REMOVED
 FROM PLANS WHICH WERE THE REQUIRED BATTERY BACK UP
 FIXTURES FROM THE STAIRWAYS. PLEASE SEE THAT SOME SORT
 OF BATTERY BACK UP FIXTURES WILL BE REQUIRED AS
 REQUIRED AND SHOWN ON ORIGINAL PLANS.
  
 2) NOTE: PLEASE SEE THE NEW PROPOSED SERVICE FOR THE
 CHPP IS NOT YET APPROVED AS SHOWN. PLEASE SEE 230.2
 WHICH SPECIAL PERMISSION MUST FIRST BE GRANTED BY THE
 AHJ IF THE BUILDING MEETS THE EXCEPTIONS TO INSTALL NEW
 SERVICE. PLEASE KNOW AT THIS TIME THIS IS NOT
 PERMITTED.
 PLEASE SEE CHILLER PLANT STRUCTURE/AREA/BUILDING
 CONTAINS A FEEDER FROM THE OTHER ELECTRICAL SERVICE
 WHICH ISNOT PERMITTED AND/OR IF IT DOES COMES TO THE
 POINT OF BEING PERMITTED, THEN A MEANS OF DISCONNECT
 AND SIGNAGE AT THIS LOCATION FOR PANEL AUX WILL BE
 REQUIRED AT A MINIMUM.
 225.31-225.39, 230.2E ETC.
  
 3) NOTE: PLEASE SEE AS NOTED ABOVE IN NOTE #2, PLEASE
 EXPLAIN AND INDICATE ANY CONTROL WIRING OR CONDUCTORS
 OF ANY TYPE WHICH ARE BEING INSTALLED FROM THE NEW
 PROPOSED CHILLER PLANT SERVICE WHICH WILL PROCEED INTO
 THE MAIN COURTHOUSE BUILDING WHICH IS BEING FED FROM A
 COMPLETELY DIFFERENT SERVICE AND SEPARATE FPL
 TRANSFORMER.
 PLEASE SEE MIXING OF SERVICES AND MEANS OF DISCONNECTS
 REQUIRED FOR THESE CONDUCTORS OR CONTROL WIRING PER
 225.31-225.39.
 PLEASE KNOW AS MUCH OF NOTES 2 AND 3 ARE NOT KNOWN AT
 THIS TIME, THERE MAY BE COMMENTS WHICH WILL FOLLOW THIS
 REVIEW.
  
 4) NOTE: PLEASE SEE 240.4C WITH RESPECT TO THE MINIMUM
 SIZE OF THE SERVICE ENTRANCE CONDUCTORS AS WELL AS THE
 MINIMUM SIZE FOR FEEDERS FOR DEVICES RATED OVER 800A?S.
 PLEASE SEE SECTIONS AS THESE SHALL BE SIZED AT OR ABOVE
 THE MINIMUM RATING OF THE OVER CURRENT PROTECTION
 DEVICE. PLEASE SEE 310.16, 110.14.
 PLEASE CORRELATE AND ADJUST.
 PLEASE SEE THIS IS FOR ALL DEVICES OVER 800A ARE,
 INCLUDING ALL MAINS ON BUILDING. IF THE CONDUCTORS TO
 MAINS ARE BY UTILITY COMPANY THIS WOULD NOT APPLY.
  
 5) NOTE: PLEASE SUBMIT MANUFACTURE?S SPECS/CUT SHEETS
 FOR THE NEW TANK LESS WATER HEATERS/INST-HOT UNITS.
 110.3, 90.7.
  
  
 6) NOTE: PLEASE SEE MISSING FOOTER STEEL FOR CHILLER
 PLANT AREAS PER 250.32, 2500.50.
  
 7) NOTE: PLEASE SEE THERE ARE SEVERAL AREAS ON PLANS
 WHICH INDICATE A REV #3, ALTHOUGH NOTHING HAS CHANGED
 FROM THE PREVIOUS/ORIGINAL SET OF PLANS WHICH CONTAIN
 THE SAME ITEMS, WORDING ETC.
 PLEASE SEE JUST TO NAME A FEW, NOTES ON RISER SHEETS
 #3, NOTES #16-21 ETC.
 RISER FOR MAINS? ETC
 PLEASE EXPLAIN REVISION AND WHAT IS BEING REVISED SINCE
 REVISION #2, AS PLANS ARE NOT CHANGED FROM FILE/RECORD
 SET OF PLANS.
 FBC 106.1.2 ADMIN SECTION.
  
 8) NOTE: PLEASE SEE ALSO SEE NOTE ABOVE WITH RESPECT TO
 LOCATION ON PLANS NOTED FOR REVISION #1, YET CHANGES
 COULD NOT BE FOUND FROM RECORD SET OF PLANS?
  
 9) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPEOF
 WORK ON PROJECT NEEDS TO BE UPDATED AS THE SCOPE OF
 WORK FOR MANY ITEMS HAS COMPLETELY CHANGED FROM APPLIED
 AMOUNT.
 PLEASE SEE PREVIOUS FBC ADMIN SECTION 106.3.5 OR
 CURRENT CODE 108.3 BOTH OF WHICH STATE THE SAME
 REQUIREMENTS.
 THIS IS REQUIRED BEFORE ANY FURTHER REVISIONS ARE DONE
 AND VALUE WILL BE REVIEWED FOR PROJECT.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717