Plan Review Notes
Plan Review Notes For Permit 05030119
Permit Number 05030119
Review Stop B
Sequence Number 50
Notes
Date Text
2007-06-16 14:07:54BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 5/3/07 FOR EAST CANOPY ROOFING SYSTEM
 PRODUCT APPROVAL.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) NO STATEWIDE PRODUCT APPROVAL COVER SHEET WAS
 SUBMITTED FOR THE PROPOSED PRODUCT.STATEWIDE PRODUCT
 APPROVALS ARE LISTED ON THE DEPARTMENT OF COMMUNITY
 AFFAIRS WEBSITE:
 HTTP://WWW.FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
 PROVIDE A STATEWIDE PRODUCT APPROVAL COVER SHEET FOR
 THE SELECTED PRODUCT.IF THE SUBMITTED NOA# 06-0410.06
 HAS NO MATCHING STATEWIDE COVER SHEET A LOCAL (CITY OF
 WEST PALM BEACH) PRODUCT APPROVAL CAN BE ISSUED,
 HOWEVER PLEASE SEE COMENT #2, BELOW REQUIRING RAS 117
 CALCULATIONS.
  
 2) THIS COMMENT APPLIES IF IT IS STILL YOUR INTENTION
 TO USE THE SUBMITTED NOA# 06-0410.06 (SEE COMMENT #1,
 ABOVE).SHEET 43 OF THE SUBMITTED PRODUCT APPROVAL
 STATES THAT THE MAXIMUM DESIGN PRESSURE IS "52.5 PSF
 (SEE GENERAL LIMITATION #7)".THE DESIGN PRESSURE FOR
 ZONE 3 OF THIS ROOF EXCEEDS 52.5 PSF SO GENERAL
 LIMITATION #7 MUST BE USED TO ALLOW ENHANCED FASTEBER
 SPACING IN ZONE 3.GENERAL LIMITATION #7 (ON SHEET 44
 OF THE SUBMITTED PRODUCT APPROVAL)REQUIRES THAT
 ENHANCE FASTENER SPACING MUST BE JUSTIFIED BY RAS 117
 CALCULATIONS PREPARED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.SUBMIT
 RAS 117 CALCULATIONS PREPARED BY AN ARCHITECT OR
 ENGINEER.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  
  
  
  