Plan Review Notes
Plan Review Notes For Permit 05030119
Permit Number 05030119
Review Stop M
Sequence Number 4
Notes
Date Text
2006-09-25 00:00:00----------------PROVISO-----------------
 1.PAGE M202:PROVIDE LOUVER AND PLENUM
 SIZE INFORMATION FOR 12X10 EXHAUST DUCT
 UP FROM 1ST FLOOR TO EXTERIOR WALL.
  
 2.PAGE M204: E.F.1 ON ROOF TO COMPLY
 WITH FBC,M 304.8 AND 306.5.A GUARD
 WILL BE REQUIRED ON ROOF IF FAN IS
 WITHIN 10' OF ROOF EDGE.
  