Plan Review Notes For Permit 05030119 |
Permit Number |
05030119 |
|
Review Stop |
FIRE |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2006-10-06 00:00:00 | ***PROVISO*** | | | | 1) THE 20' FIRE ACCESS INCLUDING | | STABILIZED SOD SHALL BE CAPABLE OF | | SUPPORTING 32 TONS. PLEASE SEE PAGE C-1. | | | | 2) THE FDC SHOWN ON PAGE C-2 SHALL BE | | WITHIN 150' OF A FIRE HYDRANT. | | | | 3) FIRE LINE BACKFLOW DEVICE SHALL BE | | EQUIPPED WITH TAMPER SWITCHES AND CHAIN | | AND LOCKS. | | | | 4) BUILDING ADDRESS NOTE ON PAGE A-0.02 | | SHOULD INCLUDE AT LEAST 1" WIDTH | | NUMBERS. | | | | 5) BUILDING ADDRESS LOCATION NOT CALLED | | OUT ON PAGE A-4.01 ON THE WEST PORTICO. | | | | 6) SEPARATE SHOP DRAWINGS AND PERMIT | | REQUIRED FOR FIRE ALARM SYSTEM. | | | | 7) ANY SECURITY DEVICES PLANNED SHALL | | NOT INTERFERE WITH ANY EXITING FROM THE | | BUILDING. | | | | 8) NO COMBUSTIBLES ALLOWED IN ANY RETURN | | AIR PLENUM. | | | | 9) ALL FIRE DAMPERS AFTER INSTALLATION | | TO BE DROP TESTED TO ENSURE PROPER | | FUNCTIONING. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW (561) 805-6722 | | PLAN REVIEW DONE BY MIKE CARSILLO | | CHIEF FIRE PREVENTION OFFICER |
|